• With maintenance-free CO2 sensing element based on optical infrared absorption
measurement (NDIR1)
• and – depending on the type of sensor – VOC2) sensing element, based on a
heated tin dioxide semiconductor
• CO2 temperature and CO2 humidity-temperature multisensor
• No recalibrations required
• Operating voltage AC 24 V or DC 15…35 V
• Signal outputs DC 0...10 V

In air ducts of ventilation and air conditioning plant to enhance room comfort and to
optimize energy consumption by providing demand-controlled ventilation. The sensor
acquires:
• CO2 concentrations
• VOC concentrations as an indication of odors in the duct air, such as tobacco smoke,
body odor, or material fumes
• The relative humidity of the duct air
• The duct air temperature
The QPM21… can be used as a:
• Control sensor in the supply or extract air duct
• Transmitter for building automation and control systems and / or display units
Typical use:
• Acquisition of CO2 and VOC concentrations:
In party rooms, lounges, fair pavillions and exhibition halls, restaurants, canteens,
shopping malls, sports gymnasiums, sales rooms, and conference rooms
• Acquisition of CO2 concentrations:
In ventilation plant of rooms with varying occupancy levels where smoking is prohibited, such as museums, theatres, movie theatres, auditoriums, office spaces and
school rooms

• The QPM21… sensors are not suited for use as safety devices, such as gas or
smoke warning devices!
• The sensors must not be used outdoors!

Type reference CO2 measuring range VOC sensitivity Temperature measuring range Humidity measuring range Measured value display
QPM2100                    0…2000 ppm   ---  ---  --- no
QPM2102              0…2000 ppm low (R1) Normal (R2) High(R3)  ---  --- no
QPM2102D  0…2000 ppm low (R1) Normal (R2) High(R3)  ---  --- yes
QPM2160    0…2000 ppm  ---  0...50 °C / −35...+35 °C  --- no
QPM2160D      0…2000 ppm  ---  0...50 °C / −35...+35 °C  --- yes
QPM2162          0…2000 ppm  ---  0...50 °C / −35...+35 °C 0---100% no
QPM2162D       0…2000 ppm  ---  0...50 °C / −35...+35 °C 0---100% yes

Product Image

Duct Air Quality Sensors 1
Img 1

Send Inquiry to this Member

Guangzhou Easycom Automation Equipment Co.,Ltd.

Huabiao Sq.,No. 601 Tianhe Rd. North , Tianhe Hi & New Tech. Development Zone, Guangzhou, China

Phone:
86-20-38473560
Fax:
86-20-38473550
Contact:
Mr. Linshi (Manager)
Mobile:
0086-20-38473560

Related Products of this Company

This member assumes full responsibility for the content of this listing. DIYTrade accepts no responsibility whatsoever in respect of such content.
To report fraudulent or illegal content, please click here.

China Suppliers Quick Searching:

Building Heater Made In China Products

,  

Building Heater China Suppliers and China Manufacturers