Model: | LEB30L-32 |
---|---|
Brand: | Legend |
Origin: | Made In China |
Category: | Electronics & Electricity / Breaker & Protector |
Label: | RCCB , residual current bre , protective breaker |
Price: |
-
|
Min. Order: | - |
Last Online:27 Jun, 2012 |
LEB30L-32 Residual Current Breakers with Overload Protection RCBs is used for protection against overload and short-circuit currents; protection against the affect of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and addational protection against direct contacts; command and isolation of rresistive and inductive loads. suitable for commercial and industrial appplications.
specification:
Rated current(A) |
Poles |
Rated sensitivity(mA) |
Voltage(V) |
Rated residual non-operating(mA) |
6 |
1P+N |
30 |
230 |
15 |
10 |
||||
16 |
||||
20 |
Technical date: Pollution degree:2
Standard :IEC 61009 protection class:IP 20
Tripping characteristic curves:B,C,D Service life at rated load:
Frequency:50 or 60Hz Electrical operations:4000
Rated insulation voltage Ui:500V Mechanical operation:4000
Rated insulation voltage Uimp:5000V Standard mounting :35mm DIN rail
Dielectric test voltage at ind .Freq. Ambient temperature:-5 ℃to +40℃
For 1min:2.0KV Storage temperature:-25 ℃to +70℃
Operating time: t≤0.1s。。。。。。。。。。。。。。。。。。breaking capacity:4500A
Connection copper section and fixing screw torque:
Rated current(A) |
Nominal cross section area S(mm²) |
Tightening torque(N.m) |
6 |
1 |
0.7 |
10 |
1.5 |
0.7 |
16 |
2.5 |
0.7 |
20 |
2.5 |
0.7 |