Model: | EJA118A |
---|---|
Brand: | YOKOGAWA |
Origin: | Made In Japan |
Category: | Electronics & Electricity / Transducer |
Label: | EJA , YOKOGAWA , JAPAN EJA |
Price: |
-
|
Min. Order: | 1 pc |
Last Online:10 Sep, 2024 |
Origin | Japan | |
Model Number | EJA118 | |
Brand Name | Yokogawa |
|
Excellent performance and stability |
|||
The EJA series uses a silicon resonant sensor formed from monocrystal silicon, a perfect material which has no hysteresis in pressure or temperature changes. The sensor minimizes overpressure, temperature change, and static pressure effects, and thus offers unmatched long-term stability. | ||||
- | Compact and light-weight design | |||
Half the weight of conventional models thanks to miniaturization of the casing with the amplifier ASIC, pressure cell structure, and flange. The ASIC uses the minimum number of parts and improves the reliability of the amplifier. | ||||
- | Fieldbus communication capability | |||
Fieldbus is a digital two-way communication system. It is a revolutionary technology for configuring instrumentation control systems and a promising successor to the standard 4 to 20 mA analog communication used in most field instruments today.
EJA series offers two types of fieldbus models, FOUNDATION™ fieldbus Low Voltage Mode and PROFIBUS PA devices, which ensure interoperability between Yokogawa and other manufactures. As for software, the EJA series incorporates two AI function blocks that compute differential and static pressures to allow flexible configuration of instrumentation. |
Specifications
EJA118W / EJA118N / EJA118Y
Diaphragm Sealed Differential Pressure Transmitters |
||||
M Capsule | H Capsule | |||
Range | -100 to 100 kPa
(-400 to 400 inH2O) |
-500 to 500 kPa
(-2000 to 2000 inH2O) |
||
Span | 2.5 to 100 kPa
(10 to 400 inH2O) |
25 to 500 kPa
(100 to 2000 inH2O) |
||
Accuracy | ±0.2% | ±0.2% | ||
Degrees of protection | IP67, NEMA 4X, and JIS C0920 immersion proof | |||
Certificates | FM, CENELEC ATEX, CSA, TIIS, IECEx | |||
Output | 4 to 20 mA DC or FOUNDATION™ fieldbus or PROFIBUS PA 2-wire system with digital communication | |||
Supply voltage | BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type)
Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity model and 9 to 17.5 V DC for FISCO model) |
|||
Ambient temperature | -40 to 60 deg C (-40 to 140 deg F) (general use type)
-30 to 60 deg C (-22 to 140 deg F) (with integral indicator) It must be within the fill fluid operating temprature range |
|||
Process temperature | -50 to 300 deg C (-58 to 572 deg F)
It must be within the fill fluid operating temprature range |
|||
Maximum working pressure | Flange rating pressure | |||
Mounting | Transmitter: 2-inch pipe mounting
Diaphragm seals: flange mounting |
|||
Process flange size | Flush type: 3-inch(80mm), 2-inch(50mm)
Extended type: 4-inch(100mm), 3-inch(80mm)
|
|||
Diaphragm material | SUS316L, Hastelloy C-276, Tantalum, Titanium | |||
Process flange material | S25C, SUS304, SUS316 | |||
Housing | Cast aluminum alloy or SUS316 equivalent stainless steel (optional) |