6 Zone Voice Evacuation Amplifier 240W
EVAC-240
Features:
Digital voice evacuation system all in one amplifier.
Specifications meet the standards of BS EN54-32 & EN608409.
EN54-16 standards certificate is under taken.
Built-in 240W 6 zone class-D amplifier.
Integration of EVAC controller, paging system, PA system & BGM system together.
Built-in two separate players for EVAC and alert voice message by SD card.
Built-in 6 zone AB speaker line low impedance supervision.
Built-in amplifier auto changeover into standby when fault.
With external amplifier input to expansion the power.
Capacity of connection 20 units remote microphone.
Red button EVAC message push to activate with priority except fireman mic.
6 zone speaker outputs with separate zone volume control (ATT).
6 zone separate indicator for EVAC, fault, music/paging & select.
System indicators of AC, DC, fault and indicators for EVAC, alert & fireman mic.
Zone capacity of 120 zones by cascaded 19 units router.
With 6 programmable control inputs and 6 programmable control outputs for voice evacuation system.
With Fault, EVAC outputs and Reset input for third party system integration.
With fireman microphone of highest priority.
Priority level: fireman mic, EVAC, input 1, remote microphone, timer & BGM.
Two combo inputs for mic/line, 4 line inputs and one REC output.
Two RJ45 ports for router, two RJ45 for remote microphone input and two RJ45 for LAN/WAN/Internet network.
IP network module for optional to buy.
AC 230V and DC24V battery input. Auto switch into the battery backup when AC fails.
Specifications:
Model |
EVAC-240 |
EVAC-500 |
|
Description |
6 Zone Voice Evacuation Amplifier |
||
Rated Power Output |
240W |
500W |
|
Fireman Microphone |
5Mv, 600Ω |
||
Line 1-2 Inputs |
385mV, 10kΩbalanced Combo |
||
Line 3-6 Inputs |
350mV, 10kΩ, RCA |
||
Frequency Response |
80Hz~20kHz |
||
THD |
<1% at RMS,1KHz |
||
S/N Ratio |
>70dB |
||
Speaker Output |
100V AB 8 zone speaker outputs |
||
REC Output |
200mV |
||
Control Input & Output |
6 programmable control inputs: Max 3.3V (voltage mode) or 0V closed contact 6 programmable control outputs: 0V closed contact Control output for fault & EVAC: 0V closed contact Reset control input: 0V closed contact |
||
Voice Message |
MP3 or WMA format, two separate players of SD card with protection cover, programmable voice message up to 255, 10 years valid |
||
Event Record |
HEX format, Hard Flash memory, events up to 1000 records, 10 years valid |
||
Operation Environment |
Operation Temp: +5℃ ~ +40℃ Store Temp: -20℃ ~ +70℃ Operation Humidity: <95% |
||
Power Consumption |
300W |
600W |
|
Power Supply |
AC230V or 115V & DC24V battery inputs, 50-60HZ |
||
AC Fuse |
250V/6.3A, slow type and restorable fuse |
||
Dimension |
484(W)×132(H)×449(D) mm |
||
Weight |
21kg |
24kg |