Home > Products > Electronics & Electricity > Optical Fiber, Cable & Wire > Electric Wire & Cable

Nuclear power cable- Cable for Nuclear Power Station 1Nuclear power cable- Cable for Nuclear Power Station 2Nuclear power cable- Cable for Nuclear Power Station 3Nuclear power cable- Cable for Nuclear Power Station 4Nuclear power cable- Cable for Nuclear Power Station 5
  • Nuclear power cable- Cable for Nuclear Power Station 1
  • Nuclear power cable- Cable for Nuclear Power Station 2
  • Nuclear power cable- Cable for Nuclear Power Station 3
  • Nuclear power cable- Cable for Nuclear Power Station 4
  • Nuclear power cable- Cable for Nuclear Power Station 5

Nuclear power cable- Cable for Nuclear Power Station

Model:-
Brand:BAOSHIDA
Origin:Made In China
Category:Electronics & Electricity / Optical Fiber, Cable & Wire / Electric Wire & Cable
Label:Nuclear power cable , BAOSHIDA , manufacture
Price: US $80 / meter
Min. Order:1 meter
Inquire Now

Member Information

Detail

ShanDong BaoShiDa Cable Co.,Ltd

Free MemberShan Dong - China
Last Online:05 Jan, 2017

Product Description

Product Name Cable for Nuclear Power Station

Product standard 
Enterprise standard (This product is manufactured as per the standard of RCC-E)。

Application 
This product is used as 1E-class circuit for the power configuration, control, testing, communications and instrument compensation of nuclear island factory building of nuclear power plant.

Product characteristics 
1、Rated  voltage(U0/U):0.6/1KV.
2、Max. permissible continuous operating temperature of conductor is 90℃, while for short circuit (no more than four seconds) the temperature is 250℃.
3、The ambient temperature under installation is -10℃~40℃.
4、The permissible bending radius under installation: 
For Unshielded Cable: no less than 6 times of overall diameter 
For shielded cable: no less than 8 times of overall diameter 
5、Min. permissible ambient temperature under installation:  -40℃ 
6、Normal useful life: 50 years.
7、Special properties of cable: 
(1)The cable can undergo bundled burning test specified in GB/T18380.3 (IEC 332-3).
(2)The insulated conductor of cable can undergo vertical burning test specified in GB/T18380.1 (IEC332-1).
(3)The low smoke property of cable conforms to the regulations specified in GB/T 17651(IEC61034): light transmittance ≥60.
(4)The low halogen property of cable conforms to regulations specified in GB/T 17650.2(IEC60754-2): PH≥4.3,electrical conductivity<10μs/mm. 
8、Electric property of cable:
(1)Cable can withstand the test of AC 3500V/5min without breakdown;
(2)The resistivity of conductorρ20 not more than 0.0172410Ω·mm²/m 
(3)Insulation resistance constant: K20 not less than 3670MΩ·km、K60 not less than 367 MΩ·km、K90 not less than 36 MΩ·km.

Name, type and specifications

  1. Power cable of 6kV used for nuclear power station

  Type

Name

Copper core

Aluminum core

 

WDZA-YJWJ-K3

 

WDZA-YJLWJ-K3

Class A, Category K3 XPLE insulated PO sheathed LSOH flame-retardant power cable for Nuclear Power Station

 

WDZA-YJS-K3

 

WDZA-YJLS-K3

Class A, Category K3 XPLE insulated PO sheathed LSOH flame-retardant power cable for Nuclear Power Station

 
Type

 
Rated Voltage 

No. of  Core

Nom.area Cross-Section area

WDZA-YJWJ-K3

6/10KV

1

120~630

WDZA-YJLWJ-K3

3

35~95

WDZA-YJS-K3

WSZA-YJLS-K3

Note: The cable listed above is fire retardant of A class. For class B or C, change A accordingly.

  1. Power cable of 1000V used for nuclear power station

Type

 

Name

 

WDZA-YJWH-K3

Class A, Category K3 Copper conductor XPLE insulated PO sheathed LSOH power cable for Nuclear Power Station

 

WDZA-YJLS-K3

Class A, Category K3 Aluminum conductor XPLE insulated PO sheathed LSOH power cable for Nuclear Power Station

 

WDZA-WJWJ-K3

Class A, Category K3 Copper conductor XPLE insulated PO sheathed LSOH flame-retardant power cable for Nuclear Power Station

Type

Rated Voltage

No. of  Core

Nom.area Cross-Section area

WDZA-YJWJ-K3    WSZA-YJWJ-K3

 

 

0.6/1kV

1

50~400

WDZA-WJWJ-K3    WDZA-WJLWJ-K3

2

2.5~70

WDZA-EWJ-K3     WDZA-ELWJ-K3

3

2.5~150

WDZA-ES-K3       WDZA-ELS-K3

4

2.5~150

WDZA-WJS-K3      WDZA-WJLS-K3

3+1

3*35+1*16~3*150+1*70

WDZA-YJS-K3      WDZA-YJLS-K3

6

2*16+4*10~2*10+4*6

WDZA-SS-K3       WDZA-SLS-K3

Note: The cable listed above is fire retardant of A class. For class B or C, change A accordingly.

3Control cable of 1000V used for nuclear power station


Type

Designation

 

WDZA-KYJWJP-K3

Class A, Category K3 XPLE insulated braided shielded PO sheathed LSOH flame-retardant control cable for Nuclear Power Station

 

WDZA-KYJSP-K3

Class A, Category K3 XPLE insulated braided shielded PO sheathed LSOH control cable for Nuclear Power Station

Type

Rated Voltage

No. of  Core

Nom.area Cross-Section area

WDZA-KYJWJ(P)-K3   WDZA-KYJWJP2-K3
WDZA-KYJWJP3      WDZA-KYJS(P)-K3
WDZA-KYJSP2-K3     WDZA-KYJSP3-K3
WDZA-KSS(P)-K3      WDZA-KSSP2-K3
WDZA-KSSP3-K3      WDZA-KES(P)-K3
WDZA-KESP2-K3      WDZA-KESP3-K3
WDZA-KWJS-K3       WSZA-KWJSP-K3
WDZA-KWJP2-K3      WDZA-KWJSP3-K3

 

 

0.6/1kV

2-61

0.5

2-61

0.75

2-61

1.0

2-61

1.5

2-48

2.5

2-24

4

2-24

6

2-19

10

Note: The cable listed above is fire retardant of A class. For class B or C, change A accordingly.

Main Technical Properties


No.

Item

Unit

Norm

Test method

1

DC resistance of conductor

 

Accord with GB3956

GB/T3048.4

2

Insulation resistance constant is at K120℃ 
Insulation resistance constant is at K90℃

 

MΩ/km

3670

3.67

GB/T3048.5

3

Power frequency voltage test for power cable and control cable for 5 minutes

 

kV

 

3.5

 

GB/T3048.8

4

 Continues heat cycle test 
Test time 
Test voltage

 

h
kV

 

5000
2

 

HN33-5-28

5

  Fire-retardant property

 

 

 

5.1

Vertical burning test for insulated conductor
Time of burning
Burn area of indication

 

%

Burning for 15s,stop fire 15s,repeated 5 times <2.5

IPCEAS-19-81

5.2

Bundled burning test
Kind of test 
Over firing length of cable

 

m

 

≤2.5

 

GB/T18380.3
IEC60332-3

5.3

 Test of smoke concentration
Light transmittance

 

%

 

≥60

GB/T17651.2
IEC61034

5.4

Corrosivity of burning gas for covered material 
PH value 
Electric conductibility

 

μS/mm

 

≥4.3
≤10

IEC60754

GB/T60754

6

Nuclear environment test (for K1,K2 kind of cable only)

 

 

 

6.1

Thermal ageing test
Test temperature
Duration

 

℃ 
h

 

135±3 
950

GB/T2951.1

6.2

Humid heat test
Humidity
Temperature
Duration

 

%
℃ 
h

 

95
60±2 
48

NFC20-504

6.3

Radiation ageing time
Temperature
Accumulated dose 
Dose rate

 

℃ 
KGY
GY/S

 

70±3 
250 
0.28±0.14

IEC60544

6.4

 Earthquake test
Temperature
D≤40mm 
Bending radius  D>40mm

 

 

20
8D
12D

NFC32-021

6.5

Radiation test under LOCA accident (for K kind of cable only)
Temperature
Accumulated dose
Dose rate

 

 

℃ 
KGY
GY/S

 

 

70±3 
600 
0.28±0.14

IEC60544-2

6.6

LOCA test (for K kind of cable only)

 

pass

RCC-E


Product Image

Nuclear power cable- Cable for Nuclear Power Station 1
Img 1
Nuclear power cable- Cable for Nuclear Power Station 2
Img 2
Nuclear power cable- Cable for Nuclear Power Station 3
Img 3
Nuclear power cable- Cable for Nuclear Power Station 4
Img 4
Nuclear power cable- Cable for Nuclear Power Station 5
Img 5

Send Inquiry to this Member

ShanDong BaoShiDa Cable Co.,Ltd

No.8 Kaiyuan Road Jinan city Shandong province,China 250101

Phone:
86-531-88681868
Fax:
86
Contact:
Marina (export trader)
Mobile:
88681868

Related Products of this Company

This member assumes full responsibility for the content of this listing. DIYTrade accepts no responsibility whatsoever in respect of such content.
To report fraudulent or illegal content, please click here.

China Suppliers Quick Searching:

Electric Wire & Cable Made In China Products

,  

Electric Wire & Cable China Suppliers and China Manufacturers