Home > Products > Electronics & Electricity > Electronic Instrument > Analysis Instrument

GC Transformer Oil Dissolved Gas Analyzer 1
  • GC Transformer Oil Dissolved Gas Analyzer 1

GC Transformer Oil Dissolved Gas Analyzer

Model:GC2010SD
Brand:TOP
Origin:Made In China
Category:Electronics & Electricity / Electronic Instrument / Analysis Instrument
Label:Dissolved Gas Tester , Gas Meter , Testing Equipment
Price: US $10000 / Set
Min. Order:1 Set
Inquire Now

Member Information

Detail

Product Description

Gas Chromatography Transformer Oil Dissolved Gas Analyzer(Model: DGA2013-1 / GC2010SD / DGA2010)

Application

GC2010SD Power System Dedicated Insulation Oil and Gas Chromatography Analysis System runs by computer automatic control, all-keyboard operation and large-screen liquid crystal display according to the requirements of power system«dissolved gas component determination in insulation oil (chromatography) ,and is characterized by high-precision temperature control, stable and reliable performance, high sensitivity, good reproducibility and so on.

 

 

 The analyzer adopts double-pillar parallel shunt system ,equipped with TCD, double FID and methane conversion oven, and could achieve total analysis of nine components (H2,O2,N2,CH4,C2H2,C2H4,C2H6,CO, CO2)of dissolved gas in insulation oil by one time. The analyzer can be employed for internal fault detection of power system oil and gas equipments, cooling medium analysis of hydrogen

 

-cooled generators, impurity analysis of sulfur hexafluoride, the boiler flue gas analysis, gas analysis and environmental monitoring analysis. Due to its employment not only for special analysis, but also for general analysis, the analyzer becomes the most effective gas analytical instrument in petroleum, chemical engineering, mining and other systems.

Features

1. Large-screen LCD display; rich and intuitive displaying content; convenient to set parameters.
2. Unique microcomputer automatic ignition device.
3. Stable and reliable digital zero setting to avoid baseline instability caused by the zero setting of potentiometer.
4. Have analysis acquisition automatic start function to seriously guarantee the synchronization of analysis and acquisition.
5. Sample injector adopts ration card to guarantee accurate sample injection and good repeatability.
6. Intelligent back pullout automatic cooling system with frequency conversion function; with fast cooling speed; achieve real near room temperature operation.
7. Column adopts unique tracking temperature rising to avoid detector contamination caused by rapid heating of column chamber .
8. With gas stopping/leaking protection and prompts functions; maximize the protection for TCD tungsten and column from damage.
9. Temperature control adopts Multichannel Integration Solid-State Relay to make temperature control stable and reliable.
10. Fault self-diagnosis function. At any time to show failure cause and alarm indication.
11. Adopt microcomputer control, keyboard setting, LCD display, with memory function.
12. High performance detector and methanator. The detection capability completely meet the Electric Power Ministry’s determination of gas component content in transformer oil.
13. Adopt one injection, second diffluence column with quick analysis speed and good repeatability.
14. Double hydrogen flame design to make low content hydrocarbons and high content CO, CO2 separately detected to avoid mutual interference.
15. Adopt new type column packing material, double column temperature flow to make the C2H2 detection time quicker, sensitivity higher and analysis period shorter.

Tachnical parameters

1. Column chamber temperature: room temperature +5℃~420℃, temperature control accuracy ±0.1
2. Detection chamber temperature: room temperature+15℃~420℃, temperature control accuracy ±0.1
3. Reburner temperature: room temperature+15℃~420℃, temperature control accuracy ±0.1℃
4.TCD sensitivity, min detection concentration for H2<2ppm, O2<5ppm, N2<10ppm
5.FID detection concentration for hydrocarbons such as methane, ethylene, acetylene<0.1ppm; detection concentration for CO、CO2<2ppm。
6.TCD sensitivity, S>3000mv.ml/mg (benzene) 

Detailed Images

 

 

 

 

 

 

 


Product Image

GC Transformer Oil Dissolved Gas Analyzer 1
Img 1

Send Inquiry to this Member

Chongqing TP Oil Purification Co.,Ltd

NO.2,Zhongxing Road,Yuzhong District,Chongqing

Phone:
86-23-81690072
Fax:
86-23-81690072
Contact:
Emily (Sales)
Mobile:
18725832414

Related Products of this Company

This member assumes full responsibility for the content of this listing. DIYTrade accepts no responsibility whatsoever in respect of such content.
To report fraudulent or illegal content, please click here.

China Suppliers Quick Searching:

Analysis Instrument Made In China Products

,  

Analysis Instrument China Suppliers and China Manufacturers