Model: | WFHK008 |
---|---|
Brand: | HX |
Origin: | Made In China |
Category: | Security & Protection / Fire Fighting |
Label: | concealed sprinkler , fire sprinkler , fire sprinkler head |
Price: |
US $0.29
/ pc
|
Min. Order: | 200 pc |
Last Online:16 Nov, 2016 |
Quanzhou Winner Fire Fighting Equipment Co.Ltd is the only subsidiary corporation of Huaxia Hose manufacturer for international business. Our products cover firehoses, fire sprinklers, fire coupling and nozzles, fire hydrant, siamese connection, firefighting equipment and fire alarm valves.
Welcome to contact with us.
Product Details
Automatic SR 68 Degree 1/2 Concealed Fire Sprinkler Head
Details
1.Small size with flat cover.
2.Automatic to protect when fire temperature reaches to its demand.
3. Conceal type to beautify your home.
4.flat cover to protect sprinkler especial on where construction is complex.
Fire Sprinkler Head Introductions
Sprinkler is an important part of wet-type auto spraying system. It is usually installed inside the building and structures with light fire danger, medium fire danger and heavy fire danger, such as workshop, warehouse, hotel, shop, recreational place, hospital, cinema, office building, and garage.
The sprinkler is composed of sprinkler frame, sealant and glass bulb. It is to be installed in the protective district via ductwork, acting as a fire detector and auto sprayer. In case of fire inside the protective district, the atmosphere temperature rises up and the liquid inside the glass bulb expands after being heated and explodes after reaching the operating temperature of the glass ball. The sealant drops and the sprinkler sprays to the protective district for fire extinguishments subject to the preset shape of spraying.
Installation, Usage, and Maintenance:
During installation, should pay attention not to damage the bulb to avoid affect the thermal performance. In the process of wrench and twist, do not use spanner to wrench the supporting arm to deformation and affect the sealing performance (note: the bulb temperature can be chosen according to the needs of users)
Application:
It is usually installed in areas with fire danger, including warehouses, shopping malls, hotels, hospitals, theaters, office building, high-rise building, garages and etc.
Temperature Rating:
Nozzle Rated Temp | Max Ambient Temp | Glass Ball Color |
57°C | 27°C | Orange |
68°C | 38°C | Red |
79°C | 49°C | Yellow |
93°C | 63°C | Green |
141°C | 111°C | Blue |
182°C | 152°C | Purple |
Please pay a visit to www dot winnerfirehose dot com
Or send inquiry to eric at winnerfirehose dot com
Payment Terms: | TT/LC |
---|---|