C UK2.5B terminal block phoenix contact
Product Description
Feed-through terminal block - UK 2,5 B - 3001035
Feed-through terminal block, Connection method: Screw connection, Number of connections: 2, Cross section: 0.2 mm² - 4 mm², AWG: 24 - 12, Width: 6.2 mm, Color: gray, Mounting type: NS 35/7,5, NS 35/15
General
Number of levels |
1 |
Number of connections |
2 |
Potentials |
1 |
Nominal cross section |
2.5 mm² |
Color |
gray |
Insulating material |
PA |
Flammability rating according to UL 94 |
V0 |
Rated surge voltage |
8 kV |
Degree of pollution |
3 |
Overvoltage category |
III |
Insulating material group |
I |
Maximum power dissipation for nominal condition |
0.77 W |
Nominal current IN |
24 A |
Nominal voltage UN |
690 V |
Open side panel |
Yes |
Shock protection test specification |
IEC 60529:2001-02 |
Back of the hand protection |
guaranteed |
Finger protection |
guaranteed |
Result of surge voltage test |
Test passed |
Surge voltage test setpoint |
9.8 kV |
Result of power-frequency withstand voltage test |
Test passed |
Power frequency withstand voltage setpoint |
1.89 kV |
Result of the test for mechanical stability of terminal points (5 x conductor connection) |
Test passed |
Result of bending test |
Test passed |
Bending test rotation speed |
10 rpm |
Bending test turns |
135 |
Bending test conductor cross section/weight |
0.2 mm² / 0.2 kg |
|
2.5 mm² / 0.7 kg |
|
4 mm² / 0.9 kg |
Tensile test result |
Test passed |
Conductor cross section tensile test |
0.2 mm² |
Tractive force setpoint |
10 N |
Conductor cross section tensile test |
2.5 mm² |
Tractive force setpoint |
50 N |
Conductor cross section tensile test |
4 mm² |
Tractive force setpoint |
60 N |
Result of tight fit on support |
Test passed |
Tight fit on carrier |
NS 32/NS 35 |
Setpoint |
1 N |
Result of voltage-drop test |
Test passed |
Requirements, voltage drop |
≤ 3.2 mV |
Result of temperature-rise test |
Test passed |
Short circuit stability result |
Test passed |
Conductor cross section short circuit testing |
2.5 mm² |
Short-time current |
0.3 kA |
Conductor cross section short circuit testing |
4 mm² |
Short-time current |
0.48 kA |
Result of thermal test |
Test passed |
Proof of thermal characteristics (needle flame) effective duration |
30 s |
Relative insulation material temperature index (Elec., UL 746 B) |
130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) |
130 °C |
Static insulating material application in cold |
-60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) |
Test passed |
Flame test method (DIN EN 60695-11-10) |
V0 |
Oxygen index (DIN EN ISO 4589-2) |
> 32 % |
NF F16-101, NF F10-102 Class I |
2 |
NF F16-101, NF F10-102 Class F |
2 |
Surface flammability NFPA 130 (ASTM E 162) |
passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) |
passed |
Smoke gas toxicity NFPA 130 (SMP 800C) |
passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) |
28 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 |
HL 1 - HL 3 |
Product Image
Send Inquiry to this Member
This member assumes full responsibility for the content of this listing. DIYTrade accepts no responsibility whatsoever in respect of such content.
To report fraudulent or illegal content, please
click here.
China Suppliers Quick Searching:
,