Model: | FTech-IEC60331 |
---|---|
Brand: | TESTech |
Origin: | Made In China |
Category: | Security & Protection / Fire Fighting |
Label: | fire test machine , lab instrument , fire resistance |
Price: |
US $1
/ pc
|
Min. Order: | 1 pc |
Last Online:12 Feb, 2020 |
Description:
Fire-resistant cable refers to the cable that can keep a safe running time in the case of flame combustion.
China's national standard GB12666.6 (equivalent to IEC331) divides the fire resistance test into A, B two classes, The flame temperature of A grade is 950 ~ 1000 ℃, and the continue flaming time is 90min, B grade flame temperature is 750 ~ 800 ℃, flaming time is 90 min. In addition,tthe test specimen shall bear the rated voltage during the test.
TESTECH Fire Resistance Tester is designed according to the requirements of GB/T19216.11-2003 (alternative GB12666.6) and IEC60331-11,and used to obtain the refractory characteristics of a fire resistant cable or optical cable under flame conditions.
Model:FTech-IEC60331
User’ s Experience:
1, This cabinet is made of stainless steel, anti-smoke and gas corrosion.
2, The control system is designed with a high degree of automation, automatic ignition, temperature and time digital display, convenient to observe and record, stable and reliable.
Standards
• IEC 60331 Part 11
• IEC 60331 Part 21
• GB/T 19216
Main Features:
1, All fixtures are made of stainless steel;
2, The burner is a belt type propane blowtorch with a Venturi mixer, and the burner nozzle is length 500mm, width 15mm;
3, Those burning holes are staggered into 3 rows, and the front width is 15mm, holes diameter is 1.32mm and these holes center distance is 3.2mm;
5, One end of the specimen holder is equipped with a clamp to fix the sample, and the other end is convenient for heat transfer along the longitudinal specimen;
6, The cable sample is supported by two metal rings, and the middle length of the two rings is about 300mm;
7, An inner diameter of the sample supporting metal rings is 150mm, and the cross-sectional diameter of the ring is 10 ± 2mm.
8, The position of the burner torch from burning the bottom is not less than 200mm, and not less than 300mm from the tank wall.
Combustion System:
1, Independent standard electrical control platform;
2, With intelligent detection function, when a short circuit in the sample during the test, automatic alarm and turn off the fire source.
3, Fuse current in the experimental circuit is 2A;
4, The sample is applied to power of AV 100V ~ 1000V adjustable;
5, The time can be set free for the fire, the time recommended by standards is 90min.
Device parameters:
1, Voltage: AC 380V 3-phase, 50 / 60Hz, 30A;
2, The input voltage 0 ~ 1000V; can be adjusted;
3, The breakdown current is 2A;
4, Maximum power: 5000VA;
5. Timer: 0 ~ 999min
6, The flame temperature of 0 ~ 1100 ℃ adjustable;
7, The test load current is 0.25A, can be adjusted;
Specification
1. Size: 1,600 (W) × 850 (D) × 1,650 (H) mm
2, Console size: 600 (W) × 750 (D) × 1,200 (H) mm
3, Power: AC 380V 3-phase, 50 / 60Hz, 30A
4. Weight: 100kg