INTRODUCTION
The foam bladder tank is the main unit of the foam extinguishing system. The foam tank and the low/medium expansion foam generator construct the low/medium foam spraying system. It can also construct the high expansion total flooding extinguishing system with high expansion foam generator. It aims at fire of class A and class B, especially for fire of class B. The foam bladder tank mainly applied in occasions such as places where inflammable liquid was produced, stored and transported. It is especially suitable to put out fire caused by inflammable liquid tank or large scale of spill fire.
PRINCIPLE
The device consists of pressure tank, bladder, proportioner, pressure gauge, valves and pipeline. A pump is needed to supply pressurized water. When pressurized water flow though proportioner, a small part of water (3%-6%) flow into tank from branch pipe to press the bladder to swap out equal foam concentrate and then mix with another part of water (97%-93%) to form foam solution in proportioner and provide to foam generator.
PARAMETERS
Working Pressure Range (MPa) | 0.6~1.2 (87~174 PSI) | |
Pressure Drop (MPa) | ≤0.2 | |
Test Pressure | Strength (MPa) | 1.5 |
Sealing (MPa) | 1.32 | |
Tank Capacity (L) | 200~15000 (52~2650 Gallon) | |
Size of Proportioner (mm) | DN80~DN250 (3"~10") | |
Flow Capacity(L/S) | 4~360 (63~1513 GPM) | |
Mixing Ratio (L/S) | 3% OR 6% |
INSTALLATION
Device should be installed at places with shelter to avoid sun and rain. Ambient temperature should be within 40°C and leave enough space for operation. Device should be installed at concrete floor and fastened with anchor nuts.
Do the hydraulic test after installing. Open the tank vent valve first then fill water into bladder from concentrate draining pipe. Then close tank vent valve when bladder is full of water . Pressurize the system and keeping for 10 minutes when pressure gets test pressure, tank should have no leakage. Close water inlet valve and open water drainage valve and concentrate drainage valve to drain water away in tank and bladder. (We will do this test when products leave the
factory)
OPERATION
1) Fill Foam Concentrate
Close water inlet valve and concentrate outlet valve, then fill foam concentrate slowly from feed inlet (also can fill foam concentrate from concentrate draining pipe). Make sure bladder vent valve is open if fill foam concentrate from concentrate draining pipe. Stop the pump now and then to avoid bladder burst if air in bladder can't be vented timely. Foam concentrate should come from the same manufacturer and the same type. Close feed inlet when finished filling foam concentrate. Close water draining valve (there should be no water flow out at this time), tank vent valve and bladder vent valve. Open water draining valve 30 minutes later, it indicates that the bladder is undamaged if there is no foam concentrate flow out from water draining pipe.
2) Operation of The Device
① Start water pump to supply pressurized water for the device (biggest working pressure is
1.2MPa)
② Open water inlet valve and concentrate outlet valve to supply foam concentrate to pipeline
(proportioner), keep other valves closed.
③ Close water inlet valve and concentrate outlet valve to stop supply foam concentrate
when finished working.
④ Keep the pump working for a while to wash pipeline with fresh water .
⑤ Open tank vent valve and bladder vent valve to relieve pressure. Then close all the valves
to set the tank in standby mode.
MAINTENANCE
① To full fill the tank timely after using every time (foam concentrate should be from the same manufacture and the same type)
② Check the surface of the tank and bladder regularly to find out if there are any leakage and corrosion and check all the valves if they work flexibly. Deal with them if there are any problems.
③ Check the foam concentrate regularly to find out if it is deteriorative. Change it if it is.