Model: | GF1061 |
---|---|
Brand: | GFUVE |
Origin: | Made In China |
Category: | Electronics & Electricity / Electronic Instrument / Analysis Instrument |
Label: | current transformers , current transformer , current transformer |
Price: |
US $16000
/ pc
|
Min. Order: | 1 pc |
Last Online:02 Jun, 2021 |
Detailed Product Description
Name: |
CT PT Analyzer |
Application: |
Current Transformer And Potential Transformer Test |
Theory: |
DC Variable-frequency Methods |
LCD: |
7inch TFT Touch Color LCD |
Phase Error: |
1min Or 3min |
Ratio Error: |
0.02% Or 0.05% |
CT Raito: |
1-50000 |
PT Ratio: |
1-10000 |
Usage: |
Measurement CT And Protection CT |
Weight |
4KG |
GF1061 portable CT PT analyzer is mainly used for field or lab testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The CT PT Analyzer is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.
The CT Analyzer automatically determines all relevant current transformer values and compares the results with the selected standard. The device evaluates the current transformer as per the IEC or IEEE standard within seconds with the push of a button. its can test current transformer and potential transformer ratio error and phase error, Magnetization curve etc.
It facilitates fast and economical on-site testing and calibration of metering and protection current transformers. Manufacturers of current transformers, high voltage transformers and switchgear also use the CT Analyzer for tests during development and production.
Application
1. Measurement type current transformer
2. Protection type current transformer
3. GIS type current transformer
4. Bushing type current transformer
5. Zero sequence current transformer
6. Voltage transformer
MAIN FUNCTIONS
I. Current Transformer (CT) |
II. Voltage Transformer (PT) |
1. Magnetization curve |
1. Excitation characteristic test |
2. Transformation ratio test |
2. Transformation ratio test |
3. Polarity |
3. Polarity |
4. 5% and 10% error curve |
4. Ratio error, phase error |
5. Accuracy limiting factor (ALF) |
5. Degauss |
6. Degauss |
6. Calculation of knee point value |
7. Ratio error, phase error |
7. Actual secondary load test (burden test) |
8. Automatic calculation of excitation knee
|
8. Resistance test |
9. Actual secondary load test (burden test) |
|
10. Resistance test |
|
11. Secondary time constant (Ts) |
|
12. Remanence coefficient (Kr) |
|
13. Transient dimensioning factor (Ktd) |
|
14. Peak instantaneous error (Er) |
|
15. Magnetizing inductance (LU) |
|
16. Instruments security factor(FS) |
|
17. Composite error |
PARAMETERS
Electrical parameters |
||
Accuracy |
0.05%, 0.02% |
|
Power supply |
AC 220V±10% or AC 120V±10%, 50/60Hz or Battery |
|
Output voltage |
0-100Vrms |
|
Output current |
0-5Arms (20A peak-value) |
|
Output power |
0-400 VA (1500 VApeak) |
|
Automatic frequency variation range |
0.1-60Hz |
|
Equivalent excitation voltage |
≤5000V |
|
Accuracy |
≤0.5% |
|
Secondary winding DC resistance measurement |
Range |
0.1-1000Ω |
Accuracy |
≤0.05% |
|
Secondary actual load measurement |
Range |
5VA-1000VA |
Accuracy |
≤0.5%±0.1VA |
|
CT/PT phase error measurement |
Accuracy |
±1min (typical) / 3 min (guaranteed) |
Resolution |
0.1min |
|
CT ratio error measurement |
Range |
1-50000 |
Accuracy |
≤0.05% |
|
PT ratio error measurement |
Range |
1-10000 |
Accuracy |
≤0.05% |
|
Standards |
||
Reference standards |
GB1207-2006, GB1208-2006, GB16847-1997
|
|
Safety standards |
GB 4793.1-2007 |
|
EMC |
EMC standard 89/336/EEC |
|
FCC Subpart B of Part 15 Class A |
||
IEC 1000-4-2 /3 /4 /6 |
||
Mechanical parameters |
||
Overall dimension (L x W x H) (mm) |
280 x 250 x 160 |
|
Weight (kg) |
≤4 |
|
Environmental conditions |
||
Relative humidity |
Relative humidity 5%-95% not condensing |
|
Operating temperature |
-10°C to +50°C |
|
Storage temperature |
-20°C to +70°C |
|
Altitude |
≤1000m |