The burner controller IFD 258 -5/1W is used for the automatic ignition and flame monitoring of the intermittent combustion of the burner. Widely used in steel, machinery, glass, ceramics, plastics and chemical industrial heating systems, at the same time, it can also be used for the control of the heating system of the atmospheric burner, which can be used for the monitoring of both the ionization of electrodes and the UV flame, and can be used for the ignition and monitoring of one or two electrodes, and the threshold current of the flame monitoring can be adjusted Non-stop flame current monitoring, can be achieved after the flame failure to re-ignition or lock alarm two modes (convertible) , there are“Normal” and“Fault” feedback output. Operating voltage: 220V AC, -10/+ 10% , 50hz; power: 43VA. Output Current: Maximum 2A for each output, maximum 2.5 a total current. Fuse: 3.15 a delay H type. There are“Normal” and“Fault” two sets of feedback output: up to 2A, 253V, no internal fuse protection. Cable length: ionization monitoring longest 75m, UV monitoring: longest 100m. Flame Current: Should Be & GT. 2 ΜA, the threshold current can be adjusted in the range of 2-20 ΜA. Service Life: 270,000 million for single electrode control valves: 1 ambient temperature: -20 â ° c ~ + 60 â ° C, no condensation allowed. Protection: IP 40 weight: 510g