Model: | SDC2-200 |
---|---|
Brand: | Sanda or OEM |
Origin: | Made In China |
Category: | Electronics & Electricity / Electric Control System |
Label: | tec air conditioner , tec cooler , tec air cooler |
Price: |
US $289
/ pc
|
Min. Order: | 1 pc |
Last Online:21 Jun, 2018 |
SANDA's 300 W DC solid state air conditioner models are designed to cool your electronic and electrical controls,instruments, computer terminals, printers, telecommunications equipment, surveillance devices, cameras, laser and optical equipment and many other electronics in variety of environments. Our electronic cabinet cooler is designed for use with a wide range of enclosures and transit cases. Models are available for both indoor and outdoor use in DC power configurations. Coolers feature corrosion-resistant stainless steel construction. All are available with a variety of options.
air conditioner without outdoor unit features:
• Extremely reliable solid state construction with long lifespan
• Maintenance free design with no moving components (other than fans)
• No compressor, refrigerant or filters
• Compact size, lightweight, convenient to install and operate
• Construction (Type 304 stainless steel) for indoor or outdoor use
• Standard models to 55°C (High ambient models avail.)
• Flush-mount or recessed-mount installation
• Recommended for vertical mounting only
• DC power configurations
• Complete 12 month warranty
Technical Data
No |
Parameters |
Model No. |
||||
SDC2-200 |
SDC2-300 |
|||||
1 |
Cooling capacity |
W |
200 |
300 |
||
2 |
Heating capacity |
W |
200 |
300 |
||
3 |
Rated voltage |
V |
DC48 |
|||
4 |
Rated power |
W |
450 |
600 |
||
5 |
Rated current |
A |
8.5 |
13.6 |
||
6 |
Internal circulation air flow rate |
m3/h |
350 |
360 |
||
7 |
External circulation air flow rate |
m3/h |
600 |
640 |
||
8 |
Working range |
°C |
-20~55 |
|||
RH |
10%~95% |
|||||
9 |
Cooling/Heating |
Cooling and heating intelligent exchanging |
||||
10 |
Protection class |
IP55 |
||||
11 |
Dimension |
Width |
mm |
250 |
250 |
|
Depth |
285 |
285 |
||||
Height |
400 |
400 |
||||
12 |
Noise |
dB(A) |
60 |
60 |
Installation
air conditioner without outdoor unit Wiring and installation
A. Embedded the door mounted TEC air conditioner into the open hole from the outside of the cabinet to ensure the TEC air conditioner's mounting flange match the cabinet's installation position.
B. Use 16* M4 phillips screws sequentially align the mounting holes on the mounting flange to fix and tighten it.
C. Check the mechanical installation of the cabinet TEC air conditioner, and do electrical installation after determining correct.
Application