Model: | - |
---|---|
Brand: | - |
Origin: | Made In China |
Category: | Electronics & Electricity / Switch / Other Switches |
Label: | - |
Price: |
US $106
/ pc
|
Min. Order: | 1 pc |
Last Online:27 Feb, 2019 |
Main technical parameters Rated voltage: 12 KV Rated current: 1250A Rated power frequency withstand voltage: 42 KV Rated lightning impulse withstand voltage: 75 KV Rated short circuit breaking current: 31.5KA Rated short circuit making current(peak value): 80KA Breaking operations under rated short circuit breaking current: 30 times Rated short time withstand current: 31.5KA Rated withstand current(peak value): 80KA Rated duration of short circuit: 4S Mechanical life: 20,000 times Closing force due to bellows and atmosphere: 120±50N Force required to hold contacts opening at full stroke: 190±50N Circuit resistance at lowest rated contacts force: ≤20μΩ Storage life: 20 years Limiting abrasion of contacts: 3 mm
Mechanical requiements of vacuum circuit breaker Clearance between opening contacts: 11±1 mm Average opening speed(Contacts closing position~75% contacts opening distance): 1.1±0.2 m/s Average closing speed(30% contacts opening distance~contacts closing position): 0.6±0.2 m/s Rated contacts pressure: 3150±200 N Contacts bouncing duration at closing operation: ≤2 ms Contacts re-bouncing clearance at opening operation: ≤2 mm Synchronism of three phases: ≤1 ms
|
||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||
Mechanical requiements of vacuum circuit breaker |
||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||
|
Payment Terms: | TT/LC |
---|---|