Laboratory Water Chiller SUNDI -60℃~300℃
-60℃~300℃
A fully closed piping design, high efficiency plate heat exchanger used to reduce the demand for the thermal fluid utilization while providing the system to achieve the rapid ups and downs in temperature The whole system is a closed liquid circulation system with the expansion of container, expansion of the container and the liquid circulation is adiabatic, and do not participate in liquid circulation, only mechanical connection, regardless of the temperature is a high temperature or low temperature, the tank temperature is limited to 60℃. Therefore, during the process the risk of imbibing and volatilization of the heat conducting medium is reduced. There following advantages for the user.
Model | SUNDI-655WV | SUNDI-675WV | SUNDI-6A10WV | SUNDI-6A15WV | SUNDI-6A25WV | |
Temp. range | -60℃~+300℃ (system add pressure 3BAR) | |||||
Control Mode | Feedback PID + Our special dynamic control calculation, PLC controller | |||||
Temp. control | Process temp control and jacket temp control model | |||||
Temp. difference | Set or control the temperature difference between jacket oil and raw material process | |||||
Program Editor | 10 programs, each program can edit 42 steps. | |||||
Communication Portocol | MODBUS RTU Protocol, RS485 interface | |||||
Material temp. feedback | PT100 OR 4~20mA or communication(normal: PT100) | |||||
Temp. feedback | The temp of three points: the inlet and outlet of equipment, reactor material temp(external temp sensor) | |||||
Medium temp. acccuracy | ±0.5℃ | |||||
Material temp. accuracy | ±1℃ | |||||
Heating power kW | 5.5 | 7.5 | 10 | 15 | 25 | |
Cooling capacity kW at | 300℃ | 5.5 | 7.5 | 10 | 15 | 25 |
100℃ | 5.5 | 7.5 | 10 | 15 | 25 | |
20℃ | 5.5 | 7.5 | 10 | 15 | 25 | |
-20℃ | 4.8 | 6 | 8.2 | 12 | 25 | |
-40℃ | 2.3 | 3.1 | 4.8 | 7.8 | 18 | |
-55℃ | 0.75 | 0.9 | 1.5 | 2.8 | 6 | |
Circulation pump maxL/min bar | 50 | 50 | 110 | 110 | 150 | |
2 | 2 | 2.5 | 2.5 | 2.5 | ||
Pump | LNEYA magnetic drive pump | |||||
Compressor | Tecumseh closed compressor | Dorin semi-closed compressor | ||||
Expansion valve | Emerson thermal expansion valve/Emerson electronic expansion valve/danfoss thermal expansion valve. | |||||
Evaporator | DANFOSS/KAORI Plate heat exchanger | |||||
Operation Panel | 7-inch touch screen,show temp curve\EXCEL data output | |||||
Safety protection | Self-diagnosis function; freezer overload protection; high pressure switch, overload relay,thermal protection device, liquid low level protection, high temperature protection and temperature fault protection. | |||||
Closed circulation system | The whole system is full closed circulation, there is no oil mist at high temperature and no water vapor at low temperature, pressure do not rise up when system is running. The system will supply oil automatically at low temperature. | |||||
Refrigerant | R404A/R23 mixture,optional: R125/R23 mixture | |||||
Connection size | G3/4 | G1 | G1 | G1 | DN32 PN10 | |
Water-cooled type W(cooling water@20℃) | 1800L/H1.5bar~4bar | 2100L/H1.5bar~4bar | 3000L/H1.5bar~4bar | 4000L/H1.5bar~4bar | 8.5m³/H1.5bar~4bar | |
Dimension cm | 55*95*170 | 55*95*170 | 70*100*175 | 80*120*185 | 100*150*185 | |
Weight kg | 265 | 305 | 340 | 380 | 980 | |
Power 380V 50HZ | 10kW | 14kW | 18kW | 26kW | 40kW |
Typical application of refrigeration heating temperature control system
Dynamic thermostatic control of cold and heat source of high pressure reaction kettle, dynamic thermostatic control of double layer glass reaction kettle, and dynamic thermostatic control of cold and hot source of double-layer reactor.Microchannel reactor thermostatic control, small temperature control system, steam - feeding system temperature control, material low temperature aging test.The thermostatic control of the combined chemical cold source heat source, the cooling heating of the semiconductor equipment and the heating temperature of the vacuum chamber are controlled.
Advantages and functions of temperature control system of refrigeration
Temperature range from 120 to 350, performance superior, unique, high - precision, intelligent temperature control.High cooling power from 0.5 to 1200kW, highest production stability and repeatable results.Multi-function alarm system and safety function, use plate heat exchanger, tube type heater to increase heating and cooling rate.7-inch and 10-inch color TFT touch screen graphics display, use magnetic drive pump, no re-seal leakage problem.Full airtight system, extended thermal conductivity liquid life, very wide temperature range, no need to change liquid media.Ultra-high temperature cooling technology can be cooled directly from 300 degrees of high temperature.The principle and the function has many advantages to using staff: because only expansion of cavity in the body heat conduction medium contact with oxygen in the air (and expansion tank temperature at room temperature to 60 degrees), can achieve lower heat conduction medium absorbed by oxidation and the risk of air moisture.No heat conduction medium evaporates at high temperature, and it can be achieved -80 ~ 190 degrees, -70 ~ 220 degrees, -88 ~ 170 degrees, -55 ~ 250 degrees, -30 ~ 300 degree continuous temperature control without pressurization.
Adopt full closed pipe design, adopt high efficiency plate heat exchanger, reducing the demand for heat conduction liquid, improve the heat utilization rate of the system, reach the rapid lifting temperature.Thermal conductive medium in a closed system, with a container, expand the heat-conducting medium not participate in circulation in the container, whether high or low temperatures, expansion tank temperature to room temperature to 60 degrees, can reduce the heat conduction medium in running the risk of absorbing the moisture and volatile.