Instrumental signal cable in intrinsically safe explosion-proof circuit
Product Description
Implemented standard
Q/HY01-2005 standard is equivalent to BS5308 standard
Flame-proof property accord with GB/T18380.3 (idt.IEC60332-3).
Characteristics and Application
The product is a kind of instrumental signal cable with low capacitance, low inductance and excellent ex-Plosion characteristics. It has excellent shield property and anti-interference property. It is used in chemical industry, petrochemical, electrical power, gas engineering, mine industry in which explosion danger exists and explosion-proof safety is required. The cable is for transmitting automatic control signal.
Application characteristics
1. Rated AC voltage Uo/U: 300/500V.
2. The highest operation temperature of core:
PE insulation: 70'C XLPE insulation:90'C Fluoroplastic:200'C Silicon rubber: 180'C
3. The lowest environment temperature:
Flame-proof PVC sheath: Fixed deploying: -40'C Non-Fixed deploying: -15'C
Silicon rubber sheath: Fixed deploying: -60'C Non-Fixed deploying: -20'C
4. Mounting and deploying temperature:
Flame-proof PVC sheath: Fixed deploying: ≥0'C,
Silicon rubber sheath: ≥-40'C
5. Permitted minimum banding radius:
Not smaller than 12times of the cable diameter for copper-plastic composite tape wrapping shielded and 6 times of the cable diameter for other cables.