1MIN 工频电压(湿态)
1MIN frequency voltage (wet)
|
4KV不闪络、不击穿
4KV no flashover, no breakdown
|
4kv,1min,湿态下组合试样未闪络和击穿
4kv, 1min, under the combined sample did not wet flashover and breakdown
|
负荷循环试验
Load cycling test
|
导体加热至90-95℃,每一循环为8h,其中加热5h,冷却3h,共三次循环
Conductor heated to 90-95 ℃, each cycle is 8h, including heating 5h, cooling 3h, a total of three cycles
|
按标准要求完成三次负荷循环试验
Three times the standard required to complete load cycle test
|
工频电压试验
Frequency voltage test
|
2.4kv不闪络,不击穿
2.4kv no flashover, no breakdown
|
2.4kv,4h,组合试样未闪络和击穿
2.4kv, 4h, mix the sample without flashover and breakdown
|