一、 安裝注意事項
Installation Notices
1、 冷卻水塔噸數不得低於冷凍機噸數,且需考慮安全系統,故要大於冷凍機噸數的30%。風冷式則不需要安裝冷卻水塔
如冷凍機為10HP,冷卻水塔須為15T…………經此類推。
Tunnage of cooling water tower should be more than that of the chiller by
30% considcring the security system。You do not need to install air-cooled cooling towers
For example,if the tunnage of the chiller is 10HP,then the cooling water
tower should be 15T....and the like.
2、冷卻水塔之水管徑不得小於冷凍機之出口管徑。管徑大小可參考規格
表。
The diameter of the cooling water tower pipe should be larger than the
outlet pipe of the chiller,Refer to the size,listed in spccification.
3、冷凍機須安裝在室外通風良好之場所,且週圍空間不得小於1米,
若小於1米,會直接影響冷凍機的制冷效果。
Refrigeration machines to be installed on the outside of a well-ventilated place, and the surrounding space shall not be less than 1 m,
If it is less than 1 meter, it will directly affect the freezer cooling effect.
4、冰水系統管路不得高于冷凍機的冰水出入口,否則停機后水箱會溢水。
(請于冰水出口加裝逆止閥)
Ice water system pipeline should be lower than that of the chiller’s inlet
and outlet,otherwise water will overflow from the tank after shutting down
the machine (please install check valves in the ice water outlet).
5、冷凍機安裝處不得完全靠牆壁,須距離80公分以上,以利保養維修。
The chiller should not be installed alongside the wall.It must be away
from the wall by more than 80 centimeters for maintenance.
6、氣冷式冷凍機須放置在空氣流通、粉塵少的地方。
Air-cooling chiller should be deposited in a place with good ventilation
and less dust.
7、外主電源線不得小於冷凍主電源線,其它電源開關不得小於冷凍機內
之無熔絲開關世界安全倍數,亦不得大於50%。
For the no-fuse breaker’s world safety multiple,the outside main power
Supply wire should be higher than the freezing main wire,and other power
Supply switch should be higher than freezing inside switch but should not
be more than 50%.