測 試 項 目
TEST PROJECT
|
測 試 方 法
TEST METHOD
|
測 試 結 果
TEST RESULTS
|
1MIN 工頻電壓(濕態)
1MIN frequency voltage (wet)
|
35KV不閃絡、不擊穿
35KV no flashover, no breakdown
|
35kv,1min,濕態下組合試樣未閃絡和擊穿
45kv, 1min, under the combined sample did not wet flashover and breakdown
|
負荷循環試驗
Load cycling test
|
導體加熱至90-95℃,每一循環為8h,其中加熱5h,冷卻3h,共三次循環
Conductor heated to 90-95 ℃, each cycle is 8h, including heating 5h, cooling 3h, a total of three cycles
|
按標準要求完成三次負荷循環試驗
Three times the standard required to complete load cycle test
|
工頻電壓試驗
Frequency voltage test
|
65kv不閃絡,不擊穿
65kv no flashover, no breakdown
|
65kv,4h,組合試樣未閃絡和擊穿
65kv, 4h, mix the sample without flashover and breakdown
|
衝擊電壓試驗
Impulse voltage test
|
250KV,正負極性各10次,不閃絡,不擊穿
250KV, polarity of the 10th, no flashover, no breakdown
|
250KV正負極性各10次,組合試樣未閃絡和擊穿
250KV polarity of the 10, combined samples have not flashover and breakdown
|
負極性15MIN直流電壓試驗
Negative DC voltage test 15MIN
|
156kv不閃絡,不擊穿
156kv no flashover, no breakdown
|
156kv,15min,組合試樣未閃絡和擊穿
156kv, 15min, mix the sample without flashover and breakdown
|
局部放電試驗
Partial discharge test
|
39KV下放電量不大於20PC
39KV delegation of power is not greater than 20PC
|
A、B、C三相在39kv下放電量為4pc
A, B, C phase in the devolution of power as 4pc 39kv
|