THT-FZG generator neutral grounding resistor

THT-FZG generator neutral grounding resistor
Model:THT-FZG
Brand:THT
Origin:Made In China
Category:Electronics & Electricity / Other Electrical & Electronic
Label:grounding resistor , earthing resistor , generator resistor
Price: -
Min. Order:1 pc
Inquire Now

Product Description

1.About us:

Baoding Tianwei Hengtong Electric Co., Ltd is a one of leading manufacture in China specialize in NER or NGR neutral grounding equipments for electrical system.

 2. Purpose:

THT-FZG Neutral Grounding Resistors Enclosure is a complete set of equipment specially used for the power generator’s neutral point adapts the high resistance grounding.

 3.Design principle:

The arc grounding over-voltage occurs when the Generator main circuits have a high earth fault current. While the generator usually capable of loading low withstand voltage and easier to damage. The generator coil will sever burns if the earth current is too high. The –FZG type generator neutral grounding resistor is the most popular and safe in the practice by high resistance connecting to the earth.

 

4.Site condition:

(1)    Ambient temperature: -40°C~60°C

(2)    Altitude: less than 4000m

(3)    Relative humidity: less than 95% (25°C)

(4)    Rated frequency: 50/60HZ

 5.Properties:

(1)    Material of enclosure: stainless steel or aluminum zinc plate with high      corrosion-resistance.

(2)    Intellect controlled unit: monitor the unbalanced current, the resistor plate, the grounding transformer and the enclosure temperature, It can also transmit the earth fault information to the controlling room.

 6.Normal Parameter Table

 

Voltage Grade
        Single- phase grounding transformer     Single- phase grounding capacity  Outer-shape dimensions
10.5
10.5/0.23KV
Below 20
1400 x1450 x H
(height of cubicle depends on flange)
13.8
13.8/0.23KV
15.75
15.75/0.23KV
20
20/0.23KV
24
24/0.23KV
10.5
10.5/0.23KV
20-30
1500 x1550 x H
(height of cubicle depends on flange)
13.8
13.8/0.23KV
15.75
15.75/0.23KV
20

20/0.23KV

24

24/0.23KV

10.5
10.5/0.23KV
30-80
1700 x1750 x H
(height of cubicle depends on flange)
13.8
13.8/0.23KV
15.75
15.75/0.23KV
20

20/0.23KV

24

24/0.23KV



 7. When order, please supply:

(1)  the rated voltage, capacity and capacitive reactance of the system;

(2)  the type of the grounding transformer;

(3)  whether needs zero sequence current transformer, and its transformation ratio and capacity?

(4)  material of the enclosure, IP protectional grade, the color, installing place and the line mode.