Medium voltage AC Drive

Medium voltage AC Drive
Model:WLD-HVF
Brand:Wanlida
Origin:Made In China
Category:Electronics & Electricity / Power Supply & Distribution / Voltage Regulator
Label:AC Motor Drive , Medium voltage drive , AC Drive
Price: -
Min. Order:1 set

Product Description

Wanlida Medium Voltage AC Drive
Direct medium voltage input and output
Cascaded multi-level frequency inverter
Import IGBT 

Wanlida Medium Voltage AC Drive

Energy Saving Fields

  • Power Generation: Induced draft fan, forced draft fan, condensate pump, feed pump, primary air fan, secondary air fan, booster fan, circulating pump, mill fan, slurry pump etc
  • Cement: draft fan, high-temperature fan, air blower, dust collection fan, etc.
  • Metallurgy: blast furnace blower, slurry pump, feed water pump, dust fan, compressor etc.
  • Petroleum&Chemical: Water injection pump, crude oil pump, Compressor, fan, circulation pump, etc
  • Urban water supply: Water delivery pump, water intake pump, water supply pump, sewage treatment industry, self-fractionating pump etc
  • Minerals & Mining: Mud pump, ventilation fan, slurry pump etc
    Others: Loads such as fan, pump and compressor in pharmaceutical, paper making and wind tunnel test.

Especially for: Fan and Pump

Power Plant

Pump, Fans

Steel Plant

Fans

Cement Plant

Fans

Product Structure

Wanlida Medium Voltage AC drive consists of By-pass cabinet, Transformer cabinet, power unit cabinet and controller cabinet from left to right.

Technical advantages

  • No need of extra output filtering device
  • Directly driving the general medium voltage synchronous or asynchronous motor and the temperature of the motor will not be increased.
  • No need of motor derating operation
  • No dv/dt damage to insulation of motor and cable
  • No torque ripple induced by harmonics, and the service life of motors and mechanism devices can be extended
  • No cable length limited when voltage drop is in the allowable range.

Besides the above advantages, Wanlida medium voltage AC drive has the following functions and features:

  • Protection of overload, overheat, over-current, open-phase, grounding, over-voltage, negative sequence.
  • Current limited function
  • Interlock protection of control power supply
  • Two sets of control power hot standby for redundancy
  • Power cell by-pass function
  • Control cabinet automatic bypass function
  • Cabinet door opening alarm function
  • Lock-phase function
  • Synchronizing switch function between variable frequency and power frequency (optional)
  • Soft start of motors, no impact to mechanical equipment and network
  • Voltage source High-high variable frequency drive, it can realize No-step speed regulation, which makes the typical motors into intelligent motors.
  • High quality power input: By phase shifting of the secondary winding and multi-pulse diode rectifier, isolated powers can be acquired and supplied for power cells. (18 pulses for 3/3.3kV, 30/36 pulses for 6/6.6kV, 48/54 pulses for 10/11kV) By using the technique of multi-pulse rectifier, the harmonic current could be eliminated greatly.
  • Power cell communicate with controller through optic-fiber, completely electric isolated
  • Inner set PID regulator, can realize running in closed-loop
  • Multiple communication methods with host computer, isolated RS485 interface, standard MODBUS RTU, communication protocol, PROFIBUS DP (optional), industrial Ethernet communication protocol (optional)
  • Accurately fault records, can inquiry information and locate fault
  • Compact construction, reasonable layout (can do customer-design)
  • Very good protective design to dust, ferrum pulveratum, acid mist, moisture etc.
  • Bypass cabinethas a function of "five-protection", meanwhile, it has a pressure relief channel to ensure the safety of operators.
  • Modularized design of power units, interchangeable and easy to repair.

Technical parameters

 

Series No

Parameters

Value

1

HVF Capacity(KVA)

250~8750kVA

2

Power of adaptive motor(KW)

200~7000KW

3

Input Frequency(Hz)

45~65Hz

4

Rated input voltage(kV)

3/3.3kV/4.16kV/6/6.6kV/10/11kV (+15%~ -35%)

5

THDi at power grid

<3% (Permissible value≤4%)

6

THDu at output side

<3% (Permissible value≤5%)

7

Input power factor

>0.95%(>20% of rated load)

8

Efficiency

>97%(under a rated load)

9

Output frequency(Hz)

0.5~120Hz

10

Output frequency resolution

0.01Hz

11

Rated output current(A)

36~600A

12

Overload capability

120%(1min), 150%(3s), 200%(Immediate protection)

13

Control mode

V/F control or Vector control

14

Logical control I/O signal

16 channels respectively

15

Analog input

0~10V/4~20mA

16

Analog output

0~10V/4~20mA Optional (2 channels)

17

Boolean input/output

Communications/Default point (expandable)

18

Acc & Dec time (S)

0.1~3000s

19

Communication with host

CAN, Profibus, Modbus, RS232, RS485 etc

20

Cooling mode

Forced air cooling

21

Storage temperature

00C~450C

22

Ambient temperature

-350C~+450C

23

Ambient humidity

95%, no condensation

24

Protection grade

IP40

25

Noise

<70DB

Factory Acceptance Test Platform

Wanlida built the first-class high voltage and big capacity medium voltage AC drive test platform to realize full-load test before delivery.

Medium voltage AC Drive 1Medium voltage AC Drive 2Medium voltage AC Drive 3Medium voltage AC Drive 4Medium voltage AC Drive 5

Member Information

Zhuhai Wanlida Electric Co., ltd
Country/Region:Guang Dong - China
Business Nature:Manufacturer
Phone:15989754164
Contact:Ashley Lin (Overseas Sales)
Last Online:17 Jun, 2015