Model: | KHYS220-40KA/2 |
---|---|
Brand: | KERBS |
Origin: | Made In China |
Category: | Electronics & Electricity / Other Electrical & Electronic |
Label: | Surge protector , lightning protection , SPD |
Price: |
-
|
Min. Order: | 1 pc |
Single-Phase Power Surge Protector:10KA-40KA
1).Product Description:
This product is a single-phase parallel connection power surge protector device (called: SPD). This product is designed as
modular with artistic outline, easy wire connection and simple installation, simple maintenance, work in a relatively
harsh environment and maintaining in a long-term stability. SPD can effectively prevent over voltage and over current
which are induced by lightning or industrial noise and other factors, and other transient surge voltage on the system
or equipment or cause permanent damage or momentarily interruption and other hazards.
◆ The product use for lightning protection zone: LPZ0 area at the junction with the LPZ1 power lines of the lightning surge protection.
◆ With work instructions indicate deterioration module functions, green (normal), red (failure).
◆ This product is designed as modular with good tightness, working indicator and degradation indicator. It is convenient for connecting.
◆ With temperature control breaker, build-in over currents fuse protector, completely avoid the fire.
◆ It has lots of advantages: extremely quick respond, large intake capacity, small leakage power, long work life,
simple maintenance. It is especially suitable for harsh lightning environments.
◆ Apply to communication, television broadcasting, computer room, automatic control and mechanical equipment
and all distribution equipment lightning protection.
2) Technology Parameters:
TYPE |
KHYS220-10KA/2 |
KHYS220-20KA/2 |
KHYS220-40KA/2 |
Protection Class: |
D |
D |
C |
Max. Continuous Operating Voltage (Uc): |
275V |
275V |
275V |
Nominal Discharge Current (8/20μ s) (In): |
5KA |
10KA |
20KA |
Max. Discharge Current (8/20μs) (Imax.): |
10KA |
20KA |
40KA |
Voltage Protection Level( Up): |
≤1.0KV |
≤1.2KV |
≤1.5KV |
Response Time: |
< 25ns |
||
Leakage current: |
≤20μA |
||
Working Environment: |
Temperature -40°C~+70°C ;Relative humidity<90% |
||
indicate deterioration: |
green(normal),red(malfunction) |
||
Protection Mode: |
L-PE、N-PE (2P) |
||
Material of Outer Shell: |
Flame retardant materials |
||
Dimension : |
90×36×62mm |
||
Weight: |
0.27kg |
3).Product Installation:
1. SPD is use for to power distribution system third-level lightning protection. It is installed in parallel on into the line side of the
total power distribution equipment or the power distribution box in the buildings, with 35mm electrical lead rail, Kevin connections
can be used.Cut off the power before installation, strictly prohibit powered operation.
2. Before installation please according to installation diagram of connections,including L is phase line,N is zero line,PE is ground line,
please connect correctly.When installation is complete,close the automatic circuit breaker,check the working condition is normal or not.
3. During using lightning protection module,we should monitored and check the status display window regularly,when the display
window was red ,it means the lightning protection module failure,it should be promptly repaired or replaced.
4. Apply to indoor operation, such as outdoors installation,you must install waterproof shell.
5. All wiring must be solid and connect by electric. SPD cable: BVR≥2.5mm2, grounding line: BVR ≥ 4mm2, the lead length
should be less than 1m and the shorter the better.
6. Lightning proof grounding should be consistent with lightning protection regulatory requirements, grounding wire should be as thick
and short as possible,resistance should be less than 10Ω.
Shenzhen Kailifeng industry co.ltd | |
---|---|