Product Description

Application

1)  Three phase power SPD is suitable for system power protection, such as switching room, power distribution cabinet, switch cabinet, AC/DC distribution board, etc.

2)  Distribution box with outdoor input in the building and each floor

3)  Low voltage(200/380VAC) industrial and civil power grid

4) Automation machine room, power supply panel of converting station main control room  

Features:

1)  Big discharger current capacity, low residual voltage, quick response

2)  Lowe leakage current and rate of change

3)  Heat isolation technique, no fire disaster

4)  Apply special shock fuse pieces, with high reliability

5)  Build-in remote alarm connect point, easy to remote control

6)  With power indicator to display working condition

7)  Equipped with lightning counter, exactly to record lightning stroke

8)  temperature control protective circuit, built-in heat protection, automatic release unit

9)  3+1 protection model(L-N, N-PE), suitable for the poor power grid area

10)  Excellent international famous core component brand

11)  Achieve Kevin wiring way, precise structure, easy installation and maintain

12)  Exquisite process, can work under the hostile environment for a long time, like acid, alkali, dust, salt fog, wet, etc

Specification  

Model

AM100A

AM100B

Nominal working voltage(Un)

380V

Max continuous operating voltage(Uc)

         385VAC         

Nominal discharge currentkA

50KA

Max discharge currentkA

100kA

Protected Mode

L1, L2, L3,N-PE

L1,L2,L3-NN—PE

Protection level

2000

Response time

≤25ns

Lightning counter

099

Dimensionmm

90*145*65

Connecting diameter(mm2

6-25 mm²

Protection Level

IP20

Installation

35mm slide guide

Working conditions

Temperature:40~+85℃; Relative humidity:≤95(25); Elevation≤3km

Note: For latest information, please contact ANSUN company

 

Installation and wiring

1. L1, L2, L3,N-PE

 

2. L1, L2, L3-N,N-PE

1)  35mm slide guide installation way, indoor and close to distribution box or power cable

2)  The best wiring for AM series AC power SPD is Kevin method, also directly in parallel(the cable length should be within 0.5m to reduce lightning route). 

3)  The cable applies above 6mm² multistrand copper core insulated conductor

4)  The front of AM series is equipped with air switch and fuse air switch chooses C type tripping characteristic, about 25A rated current; the rated current of fuse should be below 50A

5)  The wiring side of alarm point is upon the base plate, the place of which connects to wire break alarm

6)  connect the input cable(from power) to the input terminal of CB in the box, then ground line of SPD to lightning protection system ground device, lower connecting wire is better, according to the standard of lightning protection project

7)  Take a ground line from ground copper bar of SPD box to connect the earth nearby, according to the standard of lightning protection project