450/750V & 600/1000V Mica+LSZH Insulated Power Cables (Single Core)
FFX100 07mZ1-R (CU/MGT+LSZH 450/750V Class 2)
FFX100 1mZ1-R (CU/MGT+LSZH 600/1000V Class 2)
APPLICATION
This cable is used in fire extinguishing systems, sprinklers, control panels, and exit lights in high-rise
buildings, hotels, hospitals, sub-ways, and public facilities.
STANDARDS
Basic design to BS 7211
FIRE PERFORMANCE
Circuit Integrity
|
IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);
CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1)
|
System circuit integrity
|
DIN 4102-12, E30 depending on lay system
|
Flame Retardance (Single Vertical
Wire Test)
|
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;
VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
|
Reduced Fire Propagation
(Vertically-mounted bundled wires
& cable test)
|
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
|
Halogen Free
|
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
|
No Corrosive Gas Emission
|
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
|
Minimum Smoke Emission
|
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
|
No Toxic gases
|
NES 02-713; NF C 20-454
|
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
450/750V & 600/1000V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2
Fire Barrier: Mica glass tape
Insulation: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
COLOUR CODE
Insulation Colour: Orange (other colors upon request)
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C – +90°C
Temperature range during installation (mobile state): -20°C – +50°C
Minimum bending radius: 6 x Overall Diameter
Electrical PROPERTIES
Dielectric test:
|
600/1000V: 3500 V r.m.s. x 5’ (core/core);
450/750V: 2500 V r.m.s. x 5’ (core/core)
|
Insulation resistance
|
20 MΩ x km (at 20°C)
|
Short circuit temperature
|
250°C
|
CONSTRUCTION PARAMETERS
Conductor
|
FFX100 07mZ1-R
|
FFX100 1mZ1-R
|
Nominal Cross Section Area
|
No./ Nominal Diameter of trands
|
Nominal
Insulation
Thickness
|
Nominal
Overall
Diameter
|
Approx.
Weight
|
Nominal
Insulation
Thickness
|
Nominal
Overall
Diameter
|
Approx.
Weight
|
mm2
|
No./mm
|
mm
|
mm
|
kg/km
|
mm
|
mm
|
kg/km
|
1.5
|
7/0.53
|
0.7
|
3.5
|
25
|
0.8
|
3.8
|
30
|
2.5
|
7/0.67
|
0.8
|
4.1
|
35
|
0.8
|
4.2
|
40
|
4
|
7/0.85
|
0.8
|
4.6
|
52
|
1
|
5.3
|
70
|
6
|
7/1.04
|
0.8
|
5.2
|
72
|
1
|
6
|
96
|
10
|
7/1.35
|
1
|
6.5
|
120
|
1
|
6.6
|
130
|
16
|
7/1.70
|
1
|
7.6
|
180
|
1
|
7.7
|
200
|
25
|
7/2.14
|
1.2
|
9
|
275
|
1.2
|
9.1
|
290
|
35
|
7/2.52
|
1.2
|
10.2
|
370
|
1.2
|
10.3
|
390
|
50
|
19/2.52
|
1.4
|
11.8
|
500
|
1.4
|
11.9
|
520
|
70
|
19/2.14
|
1.4
|
13.4
|
700
|
1.4
|
13.5
|
730
|
95
|
19.2.52
|
1.6
|
15.8
|
980
|
1.6
|
15.9
|
990
|
150
|
37/2.52
|
1.8
|
18.8
|
1500
|
1.8
|
18.9
|
1520
|
185
|
37/2.52
|
2
|
21
|
1900
|
2
|
21.2
|
1900
|
240
|
37/2.52
|
2.2
|
25.7
|
2500
|
2.2
|
25.8
|
2550
|
300
|
37/2.52
|
2.4
|
28.6
|
3140
|
2.4
|
28.8
|
3150
|
400
|
61/2.85
|
2.6
|
32
|
4000
|
2.6
|
32.2
|
4000
|
500
|
61/3.20
|
2.8
|
35.5
|
5000
|
2.8
|
35.7
|
5000
|
630
|
127/2.52
|
2.8
|
39.5
|
6300
|
2.8
|
39.7
|
6360
|
Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Conductor
crosssection
area |
Reference Method 4
(enclosed in conduit
in thermally insulating
wall etc) |
Reference
Method 3
(enclosed in
conduit on a wall or in trunking
etc) |
Reference Method 1 (clipped direct) |
Reference Method 11 (on a perforated cable tray, horizontal or
vertical) |
Reference Method 12 (free air) |
Horizontal flat spaced |
Vertical flat spaced |
Trefoil |
|
2 cables,
single-phase
a.c. or d.c. |
3 or 4
cables,
3-phase
a.c. |
2
cables,
single- |
3 or 4
cables,
3-phase
a.c. |
2 cables,
single-phase
a.c. or d.c. flat
and touching |
3 or 4
cables,
3-phase
a.c. flat
and
touching
or trefoil |
2 cables,
single
-phase a.c.
or d.c. or flat and touching |
3 or 4
cables,
3-phase
a.c. flat
and touching
or trefoil |
2 cables,
single-phase
a.c. or d.c. or 3 cables three
phase |
2 cables,
single-phase
a.c. or d.c. or
3 cables three
phase |
3 cables,
trefoil
3-phase
phase a.c. |
phase a.c.
a.c. or
d.c |
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
mm2
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
A
|
1.5
|
18
|
17
|
22
|
19
|
25
|
23
|
-
|
-
|
-
|
-
|
-
|
2.5
|
24
|
23
|
30
|
26
|
34
|
31
|
-
|
-
|
-
|
-
|
-
|
4
|
33
|
30
|
40
|
35
|
46
|
41
|
-
|
-
|
-
|
-
|
-
|
6
|
43
|
39
|
51
|
45
|
59
|
54
|
-
|
-
|
-
|
-
|
-
|
10
|
58
|
53
|
71
|
63
|
81
|
74
|
-
|
-
|
-
|
-
|
-
|
16
|
76
|
70
|
95
|
85
|
109
|
99
|
-
|
-
|
-
|
-
|
-
|
25
|
100
|
91
|
126
|
111
|
143
|
130
|
158
|
140
|
183
|
163
|
138
|
35
|
125
|
111
|
156
|
138
|
176
|
161
|
195
|
176
|
226
|
203
|
171
|
50
|
149
|
135
|
189
|
168
|
228
|
209
|
293
|
215
|
274
|
246
|
209
|
70
|
189
|
170
|
240
|
214
|
293
|
268
|
308
|
279
|
351
|
318
|
270
|
95
|
228
|
205
|
290
|
259
|
355
|
326
|
375
|
341
|
426
|
389
|
330
|
120
|
263
|
235
|
336
|
299
|
413
|
379
|
436
|
398
|
495
|
453
|
385
|
150
|
300
|
270
|
375
|
328
|
476
|
436
|
505
|
461
|
570
|
524
|
445
|
185
|
341
|
306
|
426
|
370
|
545
|
500
|
579
|
530
|
651
|
600
|
511
|
240
|
400
|
358
|
500
|
433
|
644
|
590
|
686
|
630
|
769
|
711
|
606
|
300
|
459
|
410
|
573
|
493
|
743
|
681
|
794
|
730
|
886
|
824
|
701
|
400
|
-
|
-
|
684
|
584
|
868
|
793
|
915
|
849
|
1065
|
994
|
820
|
500
|
-
|
-
|
783
|
666
|
990
|
904
|
1044
|
973
|
1228
|
1150
|
936
|
630
|
-
|
-
|
900
|
764
|
1130
|
1033
|
1191
|
1115
|
1423
|
1338
|
1069
|
Voltage Drop (Per Amp Per Meter)
Nominal
Cross
Section
Area |
2 cables
d.c. |
2 cables, single-phase a.c. |
3 or 4 cables, 3-phase a.c. |
Ref. Methods 3
and 4 (enclosed
in conduit etc,
in or on a wall) |
Ref. Methods 1
and 11 (clipped
direct or on trays
touching) |
Ref. Methods 3
and 4 (enclosed
in conduit etc,
in or on a wall) |
Ref. Methods 1, |
Ref. Methods 1 and
11 |
11 and 12
(in trefoil) |
(Flat and touching) |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
1.5
|
31
|
|
31
|
|
|
27
|
|
|
27
|
|
|
27
|
|
|
27
|
|
2.5
|
19
|
|
19
|
|
|
16
|
|
|
16
|
|
|
16
|
|
|
16
|
|
4
|
33
|
|
12
|
|
|
10
|
|
|
10
|
|
|
10
|
|
|
10
|
|
6
|
7.8
|
|
7.9
|
|
|
6.8
|
|
|
6.8
|
|
|
6.8
|
|
|
6.8
|
|
10
|
4.7
|
|
4.7
|
|
|
4.7
|
|
|
4
|
|
|
4
|
|
|
4
|
|
16
|
2.9
|
|
2.9
|
|
|
2.9
|
|
|
2.5
|
|
|
2.5
|
|
|
2.5
|
|
|
|
r
|
x
|
z
|
r
|
x
|
z
|
r
|
x
|
z
|
r
|
x
|
z
|
r
|
x
|
z
|
25
|
1.85
|
1.6
|
0.31
|
1.9
|
1.85
|
0.19
|
1.85
|
1.6
|
0.27
|
1.65
|
1.6
|
0.165
|
1.6
|
1.6
|
0.19
|
1.6
|
35
|
1.35
|
1.35
|
0.29
|
1.35
|
1.35
|
0.18
|
1.35
|
1.15
|
0.25
|
1.15
|
1.15
|
0.155
|
1.5
|
1.15
|
0.18
|
1.15
|
50
|
0.99
|
1
|
0.29
|
1.05
|
0.99
|
0.18
|
1
|
0.87
|
0.25
|
0.9
|
0.86
|
0.155
|
0.87
|
0.86
|
0.18
|
0.87
|
70
|
0.68
|
0.7
|
0.28
|
0.75
|
0.68
|
0.175
|
0.71
|
0.6
|
0.24
|
0.65
|
0.59
|
0.15
|
0.61
|
0.59
|
0.175
|
0.62
|
95
|
0.49
|
0.51
|
0.27
|
0.58
|
0.49
|
0.17
|
0.52
|
0.44
|
0.23
|
0.5
|
0.43
|
0.145
|
0.45
|
0.43
|
0.17
|
0.46
|
120
|
0.39
|
0.41
|
0.26
|
0.48
|
0.39
|
0.165
|
0.43
|
0.35
|
0.23
|
0.42
|
0.34
|
0.14
|
0.37
|
0.34
|
0.165
|
0.38
|
150
|
0.32
|
0.33
|
0.26
|
0.43
|
0.32
|
0.165
|
0.36
|
0.29
|
0.23
|
0.37
|
0.28
|
0.14
|
0.31
|
0.28
|
0.165
|
0.32
|
185
|
0.25
|
0.27
|
0.26
|
0.37
|
0.26
|
0.165
|
0.3
|
0.23
|
0.23
|
0.32
|
0.22
|
0.14
|
0.26
|
0.22
|
0.165
|
0.28
|
240
|
0.19
|
0.21
|
0.26
|
0.33
|
0.2
|
0.16
|
0.25
|
0.185
|
0.22
|
0.29
|
0.17
|
0.14
|
0.22
|
0.17
|
0.165
|
0.24
|
300
|
0.155
|
0.175
|
0.25
|
0.31
|
0.16
|
0.16
|
0.22
|
0.15
|
0.22
|
0.27
|
0.14
|
0.14
|
0.195
|
0.135
|
0.16
|
0.21
|
400
|
0.12
|
0.14
|
0.25
|
0.29
|
0.13
|
0.155
|
0.2
|
0.125
|
0.22
|
0.25
|
0.11
|
0.135
|
0.175
|
0.11
|
0.16
|
0.195
|
500
|
0.093
|
0.12
|
0.25
|
0.28
|
0.105
|
0.155
|
0.185
|
0.1
|
0.22
|
0.24
|
0.09
|
0.135
|
0.16
|
0.088
|
0.16
|
0.18
|
630
|
0.072
|
0.1
|
0.25
|
0.27
|
0.086
|
0.155
|
0.175
|
0.088
|
0.21
|
0.23
|
0.074
|
0.135
|
0.15
|
0.071
|
0.16
|
0.17
|
Note : r = conductor resistance at operating temperature
x = reactance
z = impedance |