HVD11-1.14/630 Vacuum Circuit Breaker

HVD11-1.14/630 Vacuum Circuit Breaker
Model:-
Brand:-
Origin:-
Category:Electronics & Electricity / Other Electrical & Electronic
Label:vacuum circuit break , circuit breaker , HVD11-1.14/630
Price: US $568.7 / pc
Min. Order:10 pc

Product Description

1.Product Summary
This product mainly used in 1140v or 660v three phases electrical distribution system. It is used for distribution power, circuit protection and power equipment. It is also popular in railway, mine, electricity and so on. The product structure is vertical design. Vacuum chamber, electromagnet and latched device is up-down structure. Adjustment and maintenance are easy. It has high breaking ability, high reliability and long working life. Its in and out bus bar is at the back of the circuit breaker. And the bus bar is plug-in type, can be installed as explosion-proof feed switch easily. This circuit breaker should be used together with electronic tripper.

 

2. The normal working condition

a. Ambient temperature

-5℃- +40℃

b. Altitude          

no more than 2000m

c. Humidity

Relative humidity no more than 50% (under ambient temperature: 40℃)

d. Class of pollution

3 class

e. Installation type

Main circuit Ⅲ, Control circuit Ⅱ

f. Installation condition

Vertical installation, inclination degree<15°

g. Auxiliary switch using type

AC-15, DC-13

 

3. Model No. and meaning

1.Main technical parameters

a. Rated voltage

1140v AC

b. Rated current

630A

c. Convention thermal current

630A

d. Rated short circuit breaking current

12.5KA(1140V, COSΦ=0.3)

e. Rated short circuit breaking times

16times(Closing-Opening 10 times, Opening 6 tiems)

f. Rated working frequency

50HZ

g. Electrical life

≥3000times AC-2

h. Mechanical life

≥10000times AC-2

i. Inherent closing time

≤100ms

j. Inherent opening time

≤30ms

k. Three phases unsynchronized time

<1.5ms

l. Electromagnet power on time

120~200ms

m. Resistance of single phase closing circuit 

≤100μm

n. Opening distance 

3.0~4.0mm

o. Over travel distance

1.8~2.2mm

p. Auxiliary contacts

3NO+3NC

 

(Table 1, Table 2).

Table 1 Coil parameters

 

Rated working voltage

Rated working current

Coil resistance

Closing coil

220V AC

7.2A

15Ω

Opening coil

48V DC

0.8A

60Ω

Under voltage coil

48V DC

0.1A

480Ω

 

Table 2 Power frequency withstand voltage test

 

Power frequency withstand voltage

Testing time

Main circuit fracture

10kv

1min

Phase to Phase

3500v

Main circuit to body case

3500v

Main electromagnet coil to body case

1500v

Under voltage coil, Opening coil to body case

500v

 

2. Outline dimension drawing

1. Vacuum chamber  2. Overtravel spring  3. Rotating arm  4. Screw  5. Manual tripper  6. Under voltage tripper  7. Axis shaft  8. Holding hook  9. Shunt release

HVD11-1.14/630 Vacuum Circuit Breaker 1HVD11-1.14/630 Vacuum Circuit Breaker 2HVD11-1.14/630 Vacuum Circuit Breaker 3HVD11-1.14/630 Vacuum Circuit Breaker 4HVD11-1.14/630 Vacuum Circuit Breaker 5

Member Information

Yichang habo electric co.,ltd
Country/Region:Hu Bei - China
Business Nature:Manufacturer
Phone:15572788351
Contact:Sara Li (Sales Assistant )