Three Phase Transformer DC Resistance Meter

Three Phase Transformer DC Resistance Meter
Model:-
Brand:-
Origin:-
Category:Electronics & Electricity / Electronic Instrument / Analysis Instrument
Label: -
Price: -
Min. Order:-

Product Description

GDZC Winding resistance tester(Double channel)

In the factory, it helps in determining the following :

Calculation of the I2R losses in transformer.

Calculation of winding temperature at the end of temperature rise test of transformer.

As a benchmark for assessing possible damages in the field.

It is done at site in order to check for abnormalities due to loose connections, broken strands of conductor, high contact resistance in tap changers, high voltage leads and bushings.

1.Introduction

The DC resistance of transformer is used for testing, installing and exchanging the semi-finished or finished transformer. Its also a necessity for power department  to do preventive trials. It can effectively help you to find disfigurements in the manufacturing of transformer such as the winding choosing, welding, loose joints, missing shares and hidden danger in the running. In order to meet the need of fast measurement of DC resistance, our company makes use of our technological advantage to develop the GDZC series DC resistance tester.

2.Performance Features

(1).Its suitable for large-scale transformer above240MVA in temperature rising tests.

(2).840MVA transformer low-voltage direct-resistance tester completed within 2 minutes and the data is stable and accurate.

(3). Dual-channel shows the measurement data at the same time.

(4). Each interval of 60 seconds automatically print data.

(5).Equipped with temperature conversion software, curve waveforms.

3. Technique Index

(1). Output current: 50A, 20A, 10A,5A

(2). Output voltage: 40V

(3). Range: 0 ~ 0.8Ω (50A)

          500μΩ ~ 2Ω (20A)

          1mΩ ~ 4Ω (10A)

           1mΩ ~ 8Ω (5A)

(4). Accuracy: 0.2% ± 0.2μΩ

(5).Minimum resolution: 0.1μΩ

(6).Working temperature: -20 ~ 40

(7).Environmental humidity: 80%RH, non-condensing

(8). Working Power: AC220V ± 10%, 50HZ ± 1HZ

 

 

Three Phase Transformer DC Resistance Meter 1

Member Information

CHINA HANGYU INDUSTRY CO.,LTD
Country/Region:Chong Qin - China
Business Nature:Manufacturer
Phone:13594337683
Contact:andy (sales)
Last Online:09 Oct, 2015