CONVENTIONAL FIRE ALARM PANEL

CONVENTIONAL FIRE ALARM PANEL
Model:8200-1 -2 -4
Brand:WLD
Origin:Made In China
Category:Security & Protection / Alarm
Label:FIRE ALARM PANEL , PANEL , ALARM
Price: ¥48.8 / pc
Min. Order:100 pc

Product Description

INSTALLATION

Remove the locking screw which holds the front panel door closed. Mount the panel as close as possible to the mains and zone cabling, and connect the supply accordingly. Connect the batteries as per the diagram below, and check to see that panel is slient, with only the mains healthy lamp being illuminated.(the EOL devices should still be in place at this stage).

***Should you encounter any problems at this stage, DO NOT***

*** PROCEED, but contact your supplier for assistance***

 

Any problems which the panel highlights at this stage will be due to inappropriate field wiring. MAKE SURE IT IS CHECKED FIRST.

 

Disconnect all sources of supply (including batteries).and proceed to terminate one zone to the panel. Remove the EOL device from the panel block. and fit to the last detector on the field wiring(across -ve out and +ve on the detector base). Connect the mains and batteries, and ensure the panel is silent as before. Should everything be healthy, repeat this procedure for each zonal circuit until all circuits are connected.

 

Any problems highlighted at this stage will be due to field wiring/devices connected to each zone. Re-check all cabling and devices if necessary.

                           

                       BATTERY TERMINATIONS

 

 

                

  

              

 

                        RED

 

                        BLACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 Size300×200×90mm        Fixed Size180mm

BASIC OPERATION

NORMAL OPERATING MODE

This is the default condition for the system. this mode is indicated by the green LED AC ON being illuminated while all other LEDs are extinguished. In this mode, the system will monitor and react to all alarm and fault inputs. Whenever maintenance for fault finding has been completed, the system MUST be returned to this mode.

 

ALARM MODE.

This mode is activated by the receipt of the following:

  • A smoke detector is activated
  • A heat detector is activated
  • A manual call point is activated

The sounders will operate and the internal Buzzer will sound. The common Alarm LED will illuminate, and the first LED on the zone display (FIRE) will operate.

 

TO SILENCE ALARM

  • Turn the control key to the ON position
  • Press the alarm silence(This mutes external sounders and internal buzzer, green LED is illuminated)
  • To Restart the sounders, Press EVACUATE.
  • To Cancel the fire alarm condition, press RESET.

 

NOTE:

The system can only be reset after the MUTE switch has been activated.

 

If the panel receives a new alarm during the silence, then the sounders will start operation again.  If after RESET the zones are still in an alarm condition then the fire LEDs will not be extinguished, and the sounders will operate.

 

FAULT MODE

The panel buzzer will sound if any of the following occur:

A  Detector fault

B  Zone wiring fault

C  AC mains failure

D  Battery fault or disconnected

E  Alarm output wiring fault

The fault LED that will be illuminated will depend on the fault described above.

 

EVACUATE (ALARM RESOUND)

The EVACUATE switch can be used to activate the alarm in the event of an emergency. It can also be used to re-sound an alarm after the alarm has been silenced.

 

ZONE AND DISPLAY

Each detection zone is represented by three LED’s, one Red and Two Amber

RED

AMBER   O/C

 AMBER  S/C

When red LED is illuminated, it indicates an alarm in that zone.

Indicates an open circuit fault in the field wiring of that zone.

Indicates a short circuit fault in the field wiring of that zone

 

LED TEST

This is provided to check that all fire (red LEDs) are functioniing, and that the illuminated LEDs are providing the correct information.

 

To activate this feature:

  • Press and hold the LED test button is the ON position
  • Panel will illuminate all fire Led’s. The internal Buzzer will sound.

 

NOTE:

  • When power is applied to the panel, it will enter a 30 seconds warm-up period, to stabilize smoke detector. During the period, detection of alarm and open circuit are inhabited.
  • Once the reset switch is pressed, the panel also enter warm-up period.

 

                                 FIELD EQUIPMENT TERMINATIONS

2wire/Normal Mode

 

 

 

 

 

 

 

 

 

2Wire/Remote Led Indicator

 

 

 

 

 

 

 

 

                          

GENERAL SPECIFICATIONS

        ELECTRICAL

Main Supply………………………….220v AC 50/60 Hz+10%

Battery Voltage-----------------------------24V DC

Charging Voltage Protection--------------- Resettable Fuse

Battery over discharge Protection----------------19V DC

Sounder Output------------------------------24V Nominal EOL 300K resistor

Auxiliary Contacts--------------------------30DC 1A max. NC/NO.

Mains Supply Protection---------------------Glass Fuse

Sounder Protection---------------------------- Resettable Fuse

Reverse Battery Protection--------------------Charger Resettable fuse

Zone EOL----------------------------------------3K6 Resistor

ZONAL CIRCUITS

Each zone is monitored for an open and short Circuit fault protection. These are given by separate indications on the front panel. Monitoring is achieved with a 3K6 EOL resistor which is supplied fitted. A maximum of 50 detectors per zone is permissible(10mA max.),and any number of call points.

 

                     FUSE SPECIFICATION

 

Zone 1 to Zone 4 Control Panel

Mains Fuse

1.0A(5X20mm)

Battery Fuse

300mA

Sounder1 Fuse

500mA

Sounder2 Fuse

500mA

Charging Voltage Fuse

300mA

 

SOUNDER CIRCUIT

Two Sounder circuits are provided, each being fuse protected (500mA) and monitored for open and short circuit fault condition via a 300K end of line resistorsupplied fitted. The sounder outputs are effected by any zonal alarm or the Evacuate button on the panel front. Sounder silencing is achieved by pressing the Silence buttonThe maximum loading on any sounder circuit must not exceed 500mA.

 

BATTERY STANDBY

PANEL

SUPPLY SIZE

FOR GUIDANCE ONLY. Battery required for standby times. All alarm times are 1/2 hour

CONDITIONS

 

 

Alm load

Det.Load

24+1/2

48+1/2

1-4 Zone

1.2A

0.3A

1mA/Zone

1.2Ah

1.2Ah

 

Charger Short Circuit Protection & Batteries Protection

With intelligent charger, that senses if too much current is being drawn (for instance in the case of totally discharged batteries, or the charger leads being shorted together). In such an event, the NW8200L zone panel will turn off the power to its charger circuit. 

The panel also turns off the charger when the batteries are disconnected. 

The panel also turns off the batteries when the batteries volt is less than 19V.

In the absence of the main powerThe panel can be work by the internal Bat.start key

 

                                 WARNINGS

The battery set needs to be replaced at intervals not exceeding 5 years, depending on their usage and general condition. If in doubt, replace after 4 years in services. Upon fitting a new set of batteries, the system must be allowed to charge the batteries for at least 100 hours before they can be considered to be fully charged and therefore capable of supplying adequate back-up in the even of period, but not necessarily able to meet the regulatory specifications. When fitting the battery set to the inside of the panel, they should be secured under the bracket provided to avoid any long term movement.

 

 

 

 

 

 

CONTROL PANEL TERMININATIONS

1. Sounders, Zones

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2Alarm AUX/Fault AUX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3RELAY-OUTPUT FOR BELL(SOUNDER)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                                 

 

                                                          

                                                          

4NOTE(Default): 

  

 

              

              

              

 

 

 

              

              

              

CONVENTIONAL FIRE ALARM PANEL 1CONVENTIONAL FIRE ALARM PANEL 2

Member Information

Ningbo Wan Lida electronic technology co., LTD
Country/Region:Zhe Jiang - China
Business Nature:Manufacturer
Phone:13336671716
Contact:Willy wang' (Manager)
Last Online:28 Jul, 2015