MTU Technical Data / 400V,50Hz
Natural gas genset with heat extraction from jacket water and exhaust gas (Cogeneration Module 90°/70 ℃ ) |
|||||||
Engine type |
Electrical Power(Kw) |
Bore/stroke(mm) |
Displacement(L) |
Thermal Output(Kw) |
Electrical Efficiency nel(%) |
Total Efficiency ntot(%) |
Dimension (L/H) |
ME 3066 D3 |
119 |
130/155mm |
12.36 |
198 |
34.5 |
91.9 |
3650×960×1875 |
ME 3066 L3 |
182 |
130/155mm |
12.36 |
280 |
35.0 |
88.7 |
3520×1800×2060 |
ME 3066 L3 |
201 |
130/155mm |
12.36 |
275 |
34.9 |
82.6 |
3520×1800×2060 |
ME 3066 Z5 |
220 |
130/155mm |
12.36 |
262 |
39.0 |
85.5 |
3880×1870×2140 |
ME 3042 D3 |
232 |
130/142mm |
22.56 |
358 |
35.4 |
91.8 |
3550×1810×2220 |
ME 3042 L3 |
357 |
130/142mm |
22.56 |
529 |
36.2 |
89.8 |
3700×1810×2270 |
ME 3042 Z3 |
386 |
130/142mm |
22.56 |
541 |
36.4 |
87.4 |
3700×1810×2270 |
ME 3042 Z6 |
390 |
130/142mm |
22.56 |
474 |
39.2 |
86.8 |
3850×1870×2250 |
ME 3042 Z6 |
420 |
130/142mm |
22.56 |
504 |
39.5 |
86.8 |
3850×1870×2250 |
*NOx < 500 mg/mn3 **λ =1 with 3-Way-Catalyst, NOx < 250 mg/ mn3
3) From jacket water and exhaust gas, tolerance 8% 4) Data only provided for external gas mixture cooler
|
|||||||
Natural gas genset with heat extraction from jacket water(heat recovery unit included in delivery)and exhaust gas (exhaust gas heat exchanger loose supply )
|
|||||||
Engine type |
Electrical Power(Kw) |
Bore/stroke(mm) |
Displacement(L) |
Thermal Output(Kw) |
Electrical Efficiency nel(%) |
Total Efficiency ntot(%) |
Dimension (L/H) |
AE8V4000L33 |
776 |
170/210mm |
38.16 |
823 |
42.4 |
87.3 |
5750×1990×2400 |
AE12V4000L33 |
1169 |
170/210mm |
57.24 |
1228 |
42.8 |
87.8 |
6300×1850×2400 |
AE16V4000L33 |
1560 |
170/210mm |
76.32 |
1662 |
42.8 |
88.3 |
7100×1850×2400 |
AE20V4000L33 |
1948 |
170/210mm |
95.4 |
2098 |
42.7 |
88.7 |
7600×1850×2400 |
* NOx < 500 mg/mn3 (NOx < 250 mg/mn3 available) 1) Rated power at nominal voltage, power factor = 1 and nominal frequency 2) From jacket water, tolerance 8% 3) From jacket water and exhaust gas (120°C), tolerance 8% 4) Performance data in accordance with ISO 3046, tolerance 5% 5) Referenced methane number 6) Dimensions without exhaust gas heat exchanger
|