Model |
TAN-10 |
TAN-12 |
TAN-15 |
TAN-20 |
TAN-25 |
TAN-30 |
TAN-50 |
Rated heating capacity |
kW |
38.0 |
47.0 |
58.0 |
76.0 |
92.0 |
103.0 |
182.0 |
Rated power input |
kW |
8.2 |
10.2 |
12.7 |
16.7 |
20.5 |
23.2 |
41 |
Hot water output |
T/H |
0.77 |
0.97 |
1.21 |
1.55 |
1.93 |
2.2 |
3.87 |
Input current |
A |
13.34 |
16 |
20 |
26.51 |
33.1 |
40 |
66 |
Max running current |
A |
24 |
28 |
36 |
48 |
56 |
72 |
112 |
COP |
kW/kW |
4.6 |
4.6 |
4.6 |
4.55 |
4.5 |
4.44 |
4.44 |
Rated/Max outgoing water temp |
℃ |
55℃/60℃ |
Power supply |
V/Ph/Hz |
380V/3N/50Hz |
Noise level |
dB(A) |
63 |
64 |
66 |
68 |
68 |
68 |
72 |
Unit dimension |
Length(A) |
mm |
*1500/1450 |
1500 |
1500 |
1850 |
2000 |
2000 |
2300 |
Width(B) |
mm |
*440/780 |
700 |
800 |
1000 |
1100 |
1100 |
1260 |
Height(C) |
mm |
*1705/1050 |
1350 |
1500 |
1950 |
1930 |
2070 |
2250 |
Unit Weight |
kg |
245 |
280 |
310 |
560 |
630 |
850 |
1350 |
Operating temp limits: Air |
℃ |
-15℃-43℃ |
Throttle |
|
Electronic expansion valve / Thermal expansion valve optional |
Refrigerant type |
|
R410A/R417A/R407C optional |
Refrigerant charge qty |
kg |
2.0*2 |
2.3*2 |
2.8*2 |
5.5*2 |
6.0*2 |
6.5*2 |
6.0*4 |
Compressor |
|
Hermetically sealed scroll compresor ( Copeland, Sanyo, Daikin optional ) |
Compressor qty |
pcs |
2 |
2 |
2 |
2 |
2 |
2 |
4 |
Evaporator |
|
High efficiency blue finned aluminium tube heat exchanger |
Controller |
|
LCD controller easy operation(built-in high pressure, low pressure, over heating, over current, water flow, phase protections and so on) |
Hot water side |
Heat exchanger type |
|
High efficiency tank type/ high efficiency tube in tube heat exchanger optional |
High efficiency tank type / Shell tube heat exchanger |
Water flow |
m3/h |
6.50 |
7.80 |
9.80 |
13.00 |
16.50 |
20.50 |
32.00 |
Conncetion in / out |
DN |
32 |
32 |
40 |
50 |
50 |
65 |
80 |
Test conditions:air source side DB/WB is 20℃/15℃, inlet water temp 15℃, outlet water temp 55℃. |