Sensing input |
|
Voltage |
Jumper selectable 100-130V ac 1 phase or 190-264V ac 1 phase |
Frenquency |
50-60Hz nominal |
Power input |
|
Voltage |
100-264V ac 1 phase |
Frequency |
50-60Hz nominal |
Output |
|
Voltage |
82V dc @200V ac |
Current |
continuous 4A |
transient 7.5A for 10 secs |
Resistance |
15 ohms min (10 ohms min when input volts i s less than 175ac) |
Regulation |
+/-1.0% |
Thermal Drift |
0.03% per deg. C change in AVR ambient |
Typical System Response |
AVR response 20ms |
Field current to 90% 80ms |
Machine Volts to 97% 300ms |
External Voltage Adjustment |
+/-10% with 1 k ohm 1 watt trimmer |
Increasing resistance lowers voltage |
Under frequency Protection |
Set point 94-98% Hz |
Unit power Dissipation |
12 watts maximum |
Build Up Voltage |
4 Volts @ AVR terminals |
Analogue input |
Maximum input +/-5V dc |
Sensitivity 1V for 5% Generator Volts(adjustable) |
input resistance 1k ohm |
Quadrature Droop input |
10 ohms burden |
Max. sensitivity: 0.07A for 5% droop 0 PF |
Max. input: 0.33A |
Over Excitation protection |
Set point 75V dc |
Time delay 10-15 seconds(fixed) |
Environmental |
Vibration |
20-100Hz 50mm/sec |
100Hz-2kHz 3.3g |
Operating temperature |
-40 to +70C |
Relative Humidity 0-70C |
95% |
Storage temperature |
-55 to +80C |
Notes |
1. De-rate by 12% if mounted in portrait orientation. |
2. With 4% engine governing. |
3. After 2 minutes. |
4. Generator de-rate may apply. Check with factory. |
5. Factory set, semi-sealed, jumper selectable. |
6. Any device connected to the analogue input must be fully floating(galvanically isolated form ground), with an insulation strength of 500V ac |
7. De-rate output current by 5% per degree C above 60C. |
8. Non condensing |