Mitsubishi PLC: MELSEC-L Series

Mitsubishi PLC:  MELSEC-L Series
Model:L06CPU & L02CPU
Brand:Mitsubishi
Origin:Made In China
Category:Electronics & Electricity / Electric Control System
Label:Mitsubishi CPU , L02CPU , L06CPU
Price: -
Min. Order:1 pc

Product Description

   

A   L Series CPU  Built-in I/O Features

1. L02SCPU

General-purpose output: Sink type
Program capacity: 20K steps
Basic operation processing speed: 60 ns


2. L02SCPU-P

General-purpose output: Source type
Program capacity: 20K steps
Basic operation processing speed: 60 ns
*: End cover is enclosed.
Cannot be mounted on display unit (L6DSPU), RS-232 adapter, RS-422/485 adapter.
Communication interface: 

 

3.  L02CPU

General-purpose output: Sink type
Program capacity: 20K steps
Basic operation processing speed: 40 ns

4. L02CPU-P
General-purpose output: Source type
Program capacity: 20K steps
Basic operation processing speed: 40 ns
*: End cover is enclosed.


5. L06CPU
General-purpose output: Sink type
Program capacity: 60K steps
Basic operation processing speed: 9.5 ns

 

6. L06CPU-P
General-purpose output: Source type
Program capacity: 60K steps
Basic operation processing speed: 9.5 ns
*: End cover is enclosed.


7. L26CPU
General-purpose output: Sink type
Program capacity: 260K steps
Basic operation processing speed: 9.5 ns

8. L26CPU-P
General-purpose output: Source type
Program capacity: 260K steps
Basic operation processing speed: 9.5 ns
*: End cover is enclosed.
Communication interface: 
Ethernet port and a built-in CC-Link interfaceL26CPU-BT

9. L26CPU-BT
General-purpose output: Sink type
Program capacity: 260K steps
Basic operation processing speed: 9.5 ns

10 L26CPU-PBT
General-purpose output: Source type
Program capacity: 260K steps
Basic operation processing speed: 9.5 ns
*: End cover is enclosed.


   
B. Power Supply Modules

1. L61P
Input: 100 to 240 V AC
Output: 5 V DC, 5
 

2. L63P
Input: 24 V DC
Output: 5 V DC, 5 A

3. L63SP
Input: 24 V DC
Output: 5 V DC, 5 A
Slim type
No isolation

 

C. adapter   L6ADP-R2

L6ADP-R2
Transmission speed: 115.2 kbps
GOT(HMI) connection
MELSOFT *1 connection
Predefined protocol support function
Serial communication function

 

D. RS485 adapter L6ADP-R4
Transmission speed: 115.2 kbps
GOT(HMI) connection
Predefined protocol support function
Serial Communication function

E    Input/OUTPUT  Modules

1.LX10
Number of inputs: 16 points
100 to 120 V AC

2.LX28
Number of inputs: 8 points
100 to 240 V AC
18-point terminal block

3.DC inputLX40C6
LX40C6
Number of inputs: 16 points
24 V DC
18-point terminal block

4.LX41C4
Number of inputs: 32 points
24 V DC
40-pin connector

5.LX42C4
Number of inputs: 64 points
24 V DC
40-pin connector x2
page top
Output Modules

6. Contact output  LY10R2
Number of outputs: 16 points
24 V DC/240 V AC
Rated switching current: 2 A/point
18-point terminal block

7. LY18R2A
Number of outputs: 8 points 
(all points independent)
24 V DC/240 V AC
Rated switching current: 2 A/point
18-point terminal block

8. Triac outputLY20S6
Number of outputs: 16 points
100 to 240 V AC
Max. load current: 0.6 A/point
18-point terminal block

9. LY28S1A
Number of outputs: 8 points 
(all points independent)
100 to 240 V AC
Max. load current: 1 A/point
18-point terminal block
Transistor
output


10 (Sink type) LY40NT5P
Number of outputs: 16 points
12 to 24 V DC
Max. load current: 0.5 A/point
Protection function
18-point terminal block

11  LY41NT1P
Number of outputs: 32 points
12 to 24 V DC
Max. load current: 0.1 A/point
Protection function
40-pin connector

12  LY42NT1P
Number of outputs: 64 points
12 to 24 V DC
Max. load current: 0.1 A/point
Protection function
40-pin connector x2
Transistor
output

13 (Source type) LY40PT5P
Number of outputs: 16 points
12 to 24 V DC
Max. load current: 0.5 A/point
Protection function
18-point terminal block

14 LY41PT1P
Number of outputs: 32 points
12 to 24 V DC
Max. load current: 0.1 A/point
Protection function
40-pin connector

15  LY42PT1P
Number of outputs: 64 points
12 to 24 V DC
Max. load current: 0.1 A/point
Protection function
40-pin connector x2
page top
I/O Combined Modules

16 LH42C4NT1P
Input specifications
Number of inputs: 32 points
24 V DC
40-pin connectorOutput specifications
Number of outputs: 32 points
12 to 24 V DC
Max. load current: 0.1 A/point
Protection function
40-pin connector
DC input / Transistor
output

17  LH42C4PT1P
Input specifications
Number of inputs: 32 points
24 V DC
40-pin connectorOutput specifications
Number of outputs: 32 points
12 to 24 V DC
Max. load current: 0.1 A/point
Protection function