Product Serious
|
HF
|
Model
|
HF1K
|
HF2K
|
HF3K
|
Rated Power
|
VA/W
|
1kVA / 0.7kW
|
2kVA / 1.4kW
|
3kVA / 2.1kW
|
Input
|
Nominal Voltage
|
220VAC
|
Voltage Range
|
120 ~ 300VAC
|
Frequency Range
|
46~54Hz(default), user adjustable within 40~60Hz
|
Power Factor
|
0.97
|
Connection
|
IEC320-10A inlet
|
IEC320-16A inlet
|
Output
|
Voltage
|
220VAC/230VAC/240VAC ± 2%
|
Frequency
|
Sync with input frequency. If input frequency is out the range of 46Hz – 54Hz(57Hz – 63Hz), the output frequency is 50Hz(60Hz) × (1±0.2%)Hz.
50Hz or 60Hz×(1±0.2%)Hz〔battery mode〕
|
Waveform
|
Sine Wave
|
Distortion
|
THD <3% ( linear load )、 THD <5% ( non-linear load )
|
Overload Capability
|
108%~150% for 30 sec., ³ 150% for 300 ms
|
Current Crest Ratio
|
3:1
|
Connections
|
Click here to check pictrues
|
Battery
|
Type
|
Sealed, Maintenance free, Lead-Acid (Panasonic)
|
Quantity
|
3 pieces
|
8 pieces
|
Back-up Time (Full load)
|
5 min
|
9 min
|
5 min
|
Recharge Time ?
|
5 hrs to 90% of capacity after full load discharge
|
Bypass
|
Automatic Transfer
|
on overload and UPS failure
|
Before UPS Power-on
|
Default “NO”, user adjustable to “YES”
|
Voltage Range
|
80~264VAC (Default), user adjustable within 80~286VAC
|
Transfer Time
|
0 ms; less than 4 ms from inverter to bypass and vice versa
|
LED OR LCD
|
Status ?
|
Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault
|
Audible Alarm
|
Bypass, On battery mode, Battery low, Overload, Fault
|
Acoustic Noise
|
At 1 meter distance
|
45 dB
|
50 dB
|
Communications
|
DB-9 Port
|
RS-232 Serial Interface
|
Intelligent Slot ?
|
Options: WebPower, AS400 Card or WinPower CMC
|
Network Surge Protection
|
RJ45 I/O port available for network or Fax/Modem
|
Environmental
|
Operating Temperature
|
0 ~ 40 ° C
|
Operating Humidity
|
20 ~ 90% non-condensing
|
Weight
|
Net (Kg)
|
13
|
33
|
34
|
Dimensions
|
W x D x H (mm)
|
145 x 405 x 220
|
195 x 455 x 330
|