Product Serious |
HF |
Model |
HF1K |
HF2K |
HF3K |
Rated Power |
VA/W |
1kVA / 0.7kW |
2kVA / 1.4kW |
3kVA / 2.1kW |
Input |
Nominal Voltage |
220VAC |
Voltage Range |
120 ~ 300VAC |
Frequency Range |
46~54Hz(default), user adjustable within 40~60Hz |
Power Factor |
0.97 |
Connection |
IEC320-10A inlet |
IEC320-16A inlet |
Output |
Voltage |
220VAC/230VAC/240VAC ± 2% |
Frequency |
Sync with input frequency. If input frequency is out the range of 46Hz – 54Hz(57Hz – 63Hz), the output frequency is 50Hz(60Hz) × (1±0.2%)Hz. |
50Hz or 60Hz×(1±0.2%)Hz〔battery mode〕 |
Waveform |
Sine Wave |
Distortion |
THD <3% ( linear load )、 THD <5% ( non-linear load ) |
Overload Capability |
108%~150% for 30 sec., ³ 150% for 300 ms |
Current Crest Ratio |
3:01 |
Connections |
Click here to check pictrues |
Battery |
Type |
Sealed, Maintenance free, Lead-Acid (Panasonic) |
Quantity |
3 pieces |
8 pieces |
Back-up Time (Full load) |
5 min |
9 min |
5 min |
Recharge Time ? |
5 hrs to 90% of capacity after full load discharge |
Bypass |
Automatic Transfer |
on overload and UPS failure |
Before UPS Power-on |
Default “NO”, user adjustable to “YES” |
Voltage Range |
80~264VAC (Default), user adjustable within 80~286VAC |
Transfer Time |
0 ms; less than 4 ms from inverter to bypass and vice versa |
LED OR LCD |
Status ? |
Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault |
Audible Alarm |
Bypass, On battery mode, Battery low, Overload, Fault |
Acoustic Noise |
At 1 meter distance |
45 dB |
50 dB |
Communications |
DB-9 Port |
RS-232 Serial Interface |
Intelligent Slot ? |
Options: WebPower, AS400 Card or WinPower CMC |
Network Surge Protection |
RJ45 I/O port available for network or Fax/Modem |
Environmental |
Operating Temperature |
0 ~ 40 ° C |
Operating Humidity |
20 ~ 90% non-condensing |
Weight |
Net (Kg) |
13 |
33 |
34 |
Dimensions |
W x D x H (mm) |
145 x 405 x 220 |
195 x 455 x 330 |
|
Model |
HF1KS |
HF2KS |
HF3KS |
Rated Power |
VA/W |
1kVA / 0.7kW |
2kVA / 1.4kW |
3kVA / 2.1kW |
Input |
Nominal Voltage |
220VAC |
Voltage Range |
120~ 300VAC |
Frequency Range |
50Hz ± 5%(default), user adjustable within 40~60Hz |
Power Factor |
0.98 |
Connection |
IEC320-10A inlet |
IEC320-16A inlet |
Output |
Voltage |
220VAC ± 3% |
Frequency |
Sync with input frequency. If input frequency is out the range of 46Hz – 54Hz(57Hz – 63Hz), the output frequency is 50Hz(60Hz) × (1±0.2%)Hz. |
50Hz or 60Hz×(1±0.2%)Hz〔battery mode〕 |
Waveform |
Sine Wave |
Distortion |
THD <3% ( linear load )、 THD <5% ( non-linear load ) |
Overload Capability |
108% ~ 150% for 30 sec., ³ 150% for 300 ms |
Current Crest Ratio |
3:01 |
Connections |
Click here to check pictrues |
Battery |
Type |
Sealed, Maintenance free, Lead-Acid |
Nominal DC Voltage |
36VDC |
96VDC |
Back-up Time |
Depends on the capacity of the external battery bank |
Connection |
External Battery Socket |
Bypass |
Automatic Transfer |
On overload and UPS failure |
Before UPS Power-on |
Default “NO”, user adjustable to “YES” |
Voltage Range |
80 ~ 264VAC (Default), user adjustable within 80 ~ 286VAC |
Transfer Time |
0 ms; less than 4 ms from inverter to bypass and vice versa |
LED OR LCD |
Status |
Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault |
Audible Alarm |
Bypass, On battery mode, Battery low, Overload, Fault |
Acoustic Noise |
At 1 meter distance |
45 dB |
50 dB |
Communications |
DB-9 Port |
RS-232 Serial Interface |
Intelligent Slot |
Options: WebPower, AS400 Card or WinPower CMC |
Network Surge Protection |
RJ45 I/O port available for 10 base-T network or Fax/Modem |
Environmental |
Operating Temperature |
0 ~ 40 ° C |
Operating Humidity |
20 ~ 90% non-condensing |
Weight |
Net (Kg) |
7 |
18 |
19 |
Dimensions |
W x D x H (mm) |
145 x 400 x 220 |
192 x 460 x 348 |