Model Item | DE-5000GT |
Inverter Technology | Conversion Mode | Sine-wave, Current source, High frequency PWM |
Isolation Method | Transformer-less Design * |
DC Input Data | |
Nominal DC Voltage | 360 VDC |
Max. DC input Voltage | 500 VDC |
Working range | 120VDC~500VDC ** |
Max DC input current (Each MPPT Tracker) | 17.65 Amp |
MPPT Range | 150 VDC ~ 450 VDC |
MPPT Tracker | 2 |
AC Output Data | |
Nominal AC Power | 5000 |
Max. AC Power | 5300 |
Nominal AC Voltage | AC 230V |
Output Connect Method | 1-Phase / 2-Wires(L, N, G) or 1-Phase / 3-Wires(L1, L2, G) |
AC Voltage Rang | 184~264.5Vac(Base on 230 Vac) |
Nominal AC Current | 21.7Amp |
Frequency | 50/60Hz Auto-Selection (47.5 ~ 50.2 Hz or 59.3 ~ 60.5 Hz) |
Power Factor | >0.99 with nominal AC current |
Current Distortion | Total Harmonic current : Less than 5% Single Harmonic current : Less than 3% |
Efficiency Data | |
Max. efficiency | >96% |
Euro efficiency | >94% |
CEC efficiency | >94% |
Environmental | |
Operating Temperature | -25 °C ~ + 50 °C |
-13 °F ~ 122 °F |
Humidity | 0 to 90%(Without condensation) |
Altitude | 0 ~ 2000 M / 0 ~ 6600 ft |
Mechanical | |
Dimensions (H x W x D in mm ) | 455 x 510 x 170 |
Weight (Kgs / Lbs) | 28 / 62 |
Protection Class | IP65, outdoor |
Cooling | Free Convection |
AC Connector | Terminal |
DC Connector | Multi-Contact |
Communication | |
Communication Interface | RS232 |
USB, RS485, Dry contact, TCP/IP |
Front Panel | |
LCD | Boost input Voltage/Boost input Current/Boost input Power/AC output Voltage /AC output frequency/AC output current /AC output power/AC Energy yield/Inner Temperature/Heat sink Temperature /Status message/ Error message |
LED | Leakage current fault or DC input isolation fault |
Spec. of Utility is not matches with the Utility specifications of the inverter |
Solar Cell power is greater or smaller than sleep power |
Key Pad | UP key/ Down key/ Function key/ Enter key |
Protection | |
Utility | Over/under Voltage, Over/under Frequency, Ground fault, DC Isolation fault |
Islanding operation detection | Passive : Voltage phase jump detection Active : Reactive power control |
Over Temperature | reduced output power |
Certification | |
Safety | VDE 0126-1-1, EN50178, IEC62103 |
UL1741, IEEE1547 |
EMI/EMC | EN 6 1000-6-1, EN 6 1000-6-2, EN 6 1000-6-3, EN 6 1000-6-4 |