MAIN SPECIFICATION OF GENERATOR SETS POWERED BY UK Perkins |
GENSET MODEL |
GF-PE584 |
GF-PE640 |
GF-PE720 |
Continuous output (Kw/Kva) |
584/730 |
640/800 |
720/900 |
Standby output (Kw/Kva) |
642.4/803 |
704/880 |
792/990 |
TECHNICAL DATA |
DIESEL ENGINE MODEL |
4006-23TAG2A |
4006-23TAG3A |
4008TAG1A |
Prime Power (Kw) |
620 |
679 |
762 |
Standby Power (Kw) |
697.5 |
746.9 |
857.3 |
Cylinder Number |
6 |
6 |
8 |
Cylinder arrangement |
Vertical in-line |
Vertical in-line |
Vertical in-line |
Cycle |
4 stroke |
4 stroke |
4 stroke |
Induction system |
Turbocharged and air-to-air charge cooled |
Bore (mm) |
160 |
160 |
160 |
Stroke (mm) |
190 |
190 |
190 |
Combustion system |
Direct injection |
Cooling system |
Water-cooled |
Displacement (litres) |
22.921 |
22.921 |
30.561 |
Compression ratio |
13.6:1 |
Direction of rotation |
Anti-clockwise viewed on fly wheel |
Firing order |
1,5,3,6,2,4 |
Total lubrication system capacity(litre) |
113.4 |
113.4 |
153 |
Total coolant capacity (litre) |
105 |
105 |
143 |
Alternator Model |
SWA404A |
SWA404G |
SWA404H |
Continuous output (Kw/Kva) |
584/730 |
640/800 |
720/900 |
Power efficiency |
94.90% |
93.40% |
93.50% |
Characters |
4 Pole, Rotating Field, Brushless, Self excited, H class insulation, IP21,AVR440,12 Winding leads |
Voltage regulation |
±1.0% with 4% engine governing |
Waveform distortion |
No load∠1.5% and non-distorting balanced linear load ∠5% |
THF/TIF |
∠2%/∠50 |