ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS |
1.Rated Frequency |
50/60Hz |
2.Rated Maximum Line to Line Voltage |
12kV,r.m.s |
3.Rated Power Frequency Withstand Voltage:Air
|
48kV,r.m.s |
4.Rated Impulse Withstand Voltage:Air |
95kV,Peak |
5.Rated Normal Current |
2000A |
6.Rated Short-Circuit Current(3Phase Symmetrical Basis) |
40kA,r.m.s |
7.Percentage D.C. Component of Rated S.C. Breaking Current |
50% |
8.Rated Short-Circuit Making Current |
100kA,Peak |
9.Rated Duration of Short Time Current |
3s |
10.Rated Short Time Withstand Current |
40kA,r.m.s |
11.Rated Peak Withstand Current |
100kA,r.m.s |
12.Maximum Contact Resistance at Minimum Closing Force |
20Micro ohms |
13.Capacitor Switching Capacity(Single Bank) |
400A,r.m.s |
MECHANICAL DATA |
1.Contact Force from Atmospheric Pressure |
19.8kgF |
MECHANICAL REQUIREMENTS(REF. VCB) |
1.Contact Stroke |
9±1 mm |
2.Opening Speed(average of 75 contact gap) |
0.9-1.3m/Sec |
3.Maximum Overtravel During Opening |
2mm |
4.Maximun Rebound During Opening |
2mm |
5.Closing Speed(average of last 30% contact gap) |
0.4-0.8m/Sec |
6.Maximum Contact Bounse Duration(with maximum 2 bounces) |
0.002Sec |
7.Rated Contact Compressive Force |
390-450kgF |
LIFE (ESTIMATED) |
1.Electrical Life at Rated Normal Current |
30,000Operations |
2.Electrical Life at Rated Short Circuit Current |
50Operations |
3.Mechanical Life |
30,000Operations |
4.Contact Erosion Limit |
3mm |
5.Shelf Life |
30Years |