35 kV or Lower Power Cable with XLPE Insulation

35 kV or Lower Power Cable with XLPE Insulation
Model:35 kV
Brand:TK
Origin:Made In China
Category:Electronics & Electricity / Optical Fiber, Cable & Wire / Power Cable
Label:power cable , wires & cables , cables
Price: -
Min. Order:-
Inquire Now

Product Description

  35 kV or Lower Power Cable with XLPE Insulation 

          The cable is used to transmit power on the power transmission and distribution line of A.C, 50Hz ,rated voltage 35 kv or lower, By comparison with power cable with PVC insulation ,it has not only excellent electric performance, mechanical performance, heat &  aging resistant  performance ,weather resistan performance ,chemical corrosion resistan performance ,but also simple structure,light weight ,no restriction by laying drop,and high temperature allowance for long term working (90℃)as well.  


 
Executive standard 

   
As section "extruded insulation power cable with rated voltage from 1kV(Um=1.2kV) to 35kV (Um=40.5kV)"stipulated in GB/T12706.1-2008~GB/T12706.3-2008 or IEC60502 according to the requirement of the customer.


Working Condition 

 
 1. Long-term working temperature by cable conductor is 90℃.

 
 2. Max temperature of cable conductor shall be no more than 250℃  during short circuit (the longest lasting time shall be no more than 5 seconds).

    3. Environment  temperature for installation is no less than 0℃.

   
4. Min bending radium of cable :

         It is no less than 15 times that of cable outer diameter for cable with three cores .

         It is no less than 20 times that of cable outer diameter for cable with single core.

     5. A . C. rated voltage of  Uo/U of cable is  0.6/1kV~26/35kV.

          U0: rated A.C. voltage of  conductor to earth OR between metallic shielding for cable designing ,which is called phrase voltage.

          U : rated A.C voltage between conductors for cable designing ,which is called wire voltage.

         Um : Max endurable value of "Max system voltage" for cable.


Type,Description and Application Occasion

        

Type

     Description

Application occasion

Cu

Al

YJV

YJLV

Power cable with XLPE insulation,PVC sheath

To be laid indoors ,in the tunnel ,cable furrow,pipe or under soft soil .The cable can not bear mechanical force from outside .Single core cable isn’t permitted to be laid in the magnetic pipe.

YJY

YJLY

Cable with XLPE insulation ,PE sheath

YJV22

YJLV22

Power cable with XLPE insulation,steel tape armor ,PVE sheath

To be laid underground (depth of burying : at least 0.7m above earth),the cable can bear certain mechanical force ,but it can not bear great pulling force.

YJV23

YJLV23

Power cable with XLPE insulation steel tape armored PE sheath


Note: 
         1. We also produce steel wire armored corss-linked power cable such as YJV32. YJLV63. YJV33. YJLV33 according to the requirement of the customer.

          2. Prefix "ZR"( flame retardant type ) shall be added to the original type when flame retardant
type when flame retardant type cable is needed.



The Figure of cable structure

..................



Production Scope

................


oD Size of Cable (oD: outer diameter)

.................


Main Technical Parameter of Cable 

  
Max  value of conductor DC resistance at 20℃ shall meet the requirement of category 2 conductor stipulated in GB/T3956 standard.

Nominal cross section areaof conductor  mm2

Conductor max DC resistance at 20    Ω/km

Nominal Cross section  area of conductor mm2

Conductor max DC resistance at 20    Ω/Km

Cu conductor

Al conductor

Cu conductor

Al conductor

   1.5

    12.1

    /

  95

   0.193

   0.320

   2.5

    7.41

    /

  120

   0.153

   0.253

   4

    4.61

   7.41

  150

   0.124

   0.206

   6

    3.08

   4.61

  185

   0.0991

   0.164

   10

    1.83

   3.02

  240

   0.0754

   0.125

   16

    1.15

   1.91

  300

   0.0601

   0.100

   25

    0.727

   1.2

  400

   0.0470

   0.078

   35

    0.524

   0.868

  500

   0.0366

   0.0605

   50

    0.387

   0.641

  630

   0.0283

   0.0469

   70

    0.268

   0.443

  800

   0.0221

   0.0367


A.C. Voltage Test under Power Frequency

 

Rated voltage kV

0.6/1

1.8/3

3.6/6

6/6

6/10

8.7/10

8.7/15

12/20

 

18/30

 

21/35

 

26/35

 

Tested voltage kV

3.5

6.5

12.5

21

30.5

42

63

73.5

91

Testing condition : under environment temperature for 5 min.     

Testing requirement: insulation without puncture



Partial discharging capacity shall be tested at the voltage of 1.73 U0,and its value shall be no more than that stipulated in the following table:

kV

Rated voltage

3.6/6

6/6

6/10

8.7/10

8.7/15

12/20

 

18/30

 

21/35

26/35

Test Requirement

Sensitivity 10 pc or better, Under 1.73 U0,it should not be detected any discharge exceeding declared sensitivity tested cable

35 kV or Lower Power Cable with XLPE Insulation 1

Member Information

Nanjing Rainbow wire & cable Co.,Ltd
Country/Region:Jiang Su - China
Business Nature:Manufacturer
Phone:84671159
Contact:Mr.Yang (general manager)
Last Online:28 Feb, 2013