Power Flexible Cable for telecommunication Power Spply Application

Power Flexible Cable for telecommunication Power Spply Application
Model:-
Brand:-
Origin:Made In China
Category:Electronics & Electricity / Optical Fiber, Cable & Wire / Communication Cable
Label:wires & cables , cables , power cable
Price: -
Min. Order:-
Inquire Now

Product Description

Power Flexible Cable for telecommunication Power Spply Application


      It is used to bransmit and distribute power of A .C rated voltage 0.6./1kV or lower for power system. It has not only better performance of PVC insulation power cable but also advantages of softness and flexibility as well.


Executive standard: YD/T 1173-2001


Type and Description

Type

          Description

RV

Soft power cable with Cu core, PVC insulation

RVZ

Soft power cable with Cu core, PVC insulation,flame retardance

RVV

Soft power cable with Cu core, PVC insulation and sheath

RVVZ

Soft power cable with Cu core, PVC insulation & sheath,flame retardance

RVV22

Soft power cable with Cu core, PVC insulation & sheath,steel tape armor

RVVZ22

Soft power cable with Cu core, PVC insulation & sheath,steel tape armor,flame retardance




Production scope

 

  
Type


Core number

mm2

Nominal cross section area

RV      RVZ

RVV     RVVZ

 

      1

 

1.5~400

RVV     RVVZ

RVV22   RVVZ22

 

      2

 

 1.5~185

RVV     RVVZ

RVV22   RVVZ22

 

      3

 1.5~300

 4~300

RVV     RVVZ

RVV22   RVVZ22

     

4

 

 4~185

RVV     RVVZ

RVV22   RVVZ22

    

3+1

 4~300

 4~240

RVV     RVVZ

RVV22   RVVZ22

    

3+2

 4~240

 10~240




Working Condition 

    1: Max temperature of cable conductor for Long-term working is 70
.

     
2: Min environment temperature for installing cable is 0℃.

      3: Bending radium allowed by cable : It will be no less than 8 times that of cable O.D for inarmored cable and 20 times that of cable O.D for armored cable .

      4: Max. working temperature of cable conductor is 160℃ during short circuit (the longest lasting time shall be no more than 5 seconds).



Main Technical Parameter

       
Max DC resistance value of conductor at 20℃ shall meet the requirements of the following bable:

  

Nominal cross section area (mm2)

1.5

2.5

4

6

10

16

25

35

50

Max.DC resistance of conductor at 20(Ω/km)

13.3

7.98

4.95

3.30

1.91

1.21

0.780

0.554

0.326

Nominal cross section area (mm2)

70

95

120

150

185

240

300

400

500

Max.DC resistance of conductor at 20(Ω/km)

0.272

0.206

0.161

0.129

0.106

0.0801

0.0641

0.0495

0.0391



Min insulation resistance at 70

 

(mm2)

Nominal cross section area        

(MΩ.km)

Min insulation resistance at 70

(mm2)

Nominal cross section area

(MΩ.km)

Min insulation resistance at 70

    1.5

       0.010

    70

        0.0032

    2.5

       0.009

    95

        0.0032

    4

       0.007

    120

        0.0029

    6

       0.006

    150

        0.0029

    10

       0.0056

    185

        0.0029

    16

       0.0046

    240

        0.0028

    25

       0.0044

    300

        0.0028

    35

       0.0038

    400

        0.0026

    50

       0.0037

     /

          /

 

Testing condition1.Testing length : 5m. 2.Time of immersion in the water is one hour .

                       3.Temperature of water is 70



   A.C. Voltage test under power frequency

The finished cable shall bear A.C. voltage test of 50Hz listed in the following bable without puncture.

 

 

Core NO.

Testing method

(m)

Sample length

Voltage    V

Lasting time

Rated voltage

Testing voltage

 

    

5 min

Single core

Lmmersing in the water 1h

 

Manufacturing length

 

450/750

 

2500

Multi-core and armoring

Interphase

600/1000

3500

 

*Suitable for RV type and RVZ type .



Approximate outer diameter and current loading capacity of cable

       By comparing with common power cable of the same specification with PVC insulation and sheath,cable outer diameter is bigger by 2~10mm for cable with cross section of 95mm 2 or lower and by 12~20mm for cable with cross section of 120 mm 2 or higher. And cable weitht generally remains heavier by 4%~10%. About current-loading capacity allowed by soft power cable ,you can refer to that of VV series power cable of the same specifi-cation with a drop of 6%~10%.



Delivery Length 


     Delivery length of cable depends on both agree-ments with length error allowance of ±0.5%.
Power Flexible Cable for telecommunication Power Spply Application 1

Member Information

Nanjing Rainbow wire & cable Co.,Ltd
Country/Region:Jiang Su - China
Business Nature:Manufacturer
Phone:84671159
Contact:Mr.Yang (general manager)
Last Online:28 Feb, 2013