AR-1057 / 1058 / 1068 / 1069 Features
1.Din-Rai
2.Operating Temperatures : -20 ~ +75
3.Input Power : +10VDC ~ +30VDC
4.Isolation P rotection ; 3000VDC
5.Protocol : Modbus-RTU / Modbus-ASCII
6.Output LED Indicator
AR-1057 / 1058 / 1068 / 1069 Introduction
The AR series is a family of network data acquisition and control modules that support Modbus RTU and Modbus ASCII protocols. AR series can easily communicate with most popular SCADA/ HMI software and PLC
AR-1057 / 1058 / 1068 / 1069 Pin Assignments |
Item |
AR-1057/1058 |
AR-1068/1069 |
Item |
AR-1057/1058 |
AR-1068 |
AR-1069 |
1 |
DO 7~9COM |
RL5 NO |
14 |
DO0~2 COM |
RL0 NO |
RL0 NO |
2 |
DO 7 |
RL5 COM |
15 |
DO 0 |
RL0 COM |
RL0 COM |
3 |
DO 8 |
RL5 NC |
16 |
DO 1 |
RL0 NC |
NC |
4 |
DO 9 |
RL6 NO |
17 |
DO 2 |
RL1 NO |
RL1 NO |
5 |
DO 7~9 GND |
RL16 COM |
18 |
DO 0~2 GND |
RL1 COM |
RL1 COM |
6 |
DO 10~11 COM |
RL6 NC |
19 |
DO3~4 COM |
RL1 NC |
NC |
7 |
DO 10 |
RL7 NO |
20 |
DO 3 |
RL2 NO |
RL2 NO |
8 |
DO 11 |
RL7 COM |
21 |
DO 4 |
RL2 COM |
RL2 COM |
9 |
DO 10~11 GND |
RL7 NC |
22 |
DO 3~4 GND |
RL2 NC |
RL3 NO |
10 |
(Y)DATA+ |
(Y)DATA+ |
23 |
DO 5~6 COM |
RL3 COM |
RL3 COM |
11 |
(G)DATA- |
(G)DATA- |
24 |
DO 5 |
RL3 NO |
NC |
12 |
(R)+VS |
(R)+VS |
25 |
DO 6 |
RL4 COM |
RL4 NO |
13 |
(B)GND |
(B)GND |
26 |
DO 5~6 GND |
RL4 NO |
RL4 COM |
|
AR-1057 / 1058 / 1068 / 1069 Specifications |
Interface |
|
AR 1057 |
AR1058 |
AR1068 |
AR1069 |
Output Channels |
12 |
12 |
8 |
8 |
Connectors |
2X plug-in terminal blocks(#14~28AWG) |
Power Consumption |
0.96W@24VDC |
0.96W@24VDC |
1.68W@24VDC |
2.88W@24VDC |
Supported Protocols |
Modbus-RTU/Modbus-ASCII |
Output Type |
Souce |
Sink |
Relay |
Power Relay |
Output Isolation Voltage |
3000VDC |
LED Indicators |
Yes |
Output Rating(max) |
10-35VDC/1A |
40VDC/200mA(Open Collector) |
0.5A@120VDC/1A@30V |
5A@250V/5A@30VDC |
Type |
Digital |
Digital |
6X from C/2X from A |
3X from C/5X from A |
Output off Time |
<1ms |
<1ms |
<8ms |
<8ms |
Output on Time |
<1ms |
<1ms |
<7ms |
<7ms |
Power on Set Value |
Yes(Power on output value) |
Communication fail set value |
Yes(Force the DO channels to safety status when communication in time-out and over pre-defined period) |
Casing |
Mechanical |
Plastic |
Flammability |
Fire Retardant Materials |
Dimensions(W*H*D) |
118.2mm*76.4mm*38.5mm |
Installation |
DIN-Rail |
Environment |
Operating Temperature |
-20 ~ +75 |
Storage Temperature |
-25 ~ +80 |
Humidity |
10-90%RH, no-condensing |
|