Technical Data | ||||
Property | Test method | Values | ||
Work frequency voltage withstand | 4 kV/1min | No breakdown and no flashover | ||
Load cycling (3 times) | 5hrs heating; | 2.4kV/4hrs | ||
3hrs cooling | No breakdown and no flashover | |||
Work frequency voltage withstand | 2.4kV/4hrs | No breakdown and no flashover |
Dimensions | ||||
Reference | Termination | Reference | Joint | size for conductor |
UPM C1 | UPM C1 | mm2 | ||
NSY-121 | 2 cores | JSY-121 | 2 cores | 4-35 |
NSY-122 | 2 cores | JSY-122 | 2 cores | 35-50 |
NSY-123 | 2 cores | JSY-123 | 2 cores | 70-150 |
NSY-124 | 2 cores | JSY-124 | 2 cores | 185-300 |
NSY-131 | 3 cores | JSY-131 | 3 cores | 4-35 |
NSY-132 | 3 cores | JSY-132 | 3 cores | 35-50 |
NSY-133 | 3 cores | JSY-133 | 3 cores | 70-150 |
NSY-134 | 3 cores | JSY-134 | 3 cores | 185-300 |
NSY-141 | 4 cores | JSY-141 | 4 cores | 4-35 |
NSY-142 | 4 cores | JSY-142 | 4 cores | 35-50 |
NSY-143 | 4 cores | JSY-143 | 4 cores | 70-150 |
NSY-144 | 4 cores | JSY-144 | 4 cores | 185-300 |
NSY-151 | 5 cores | JSY-151 | 5 cores | 4-35 |
NSY-152 | 5 cores | JSY-152 | 5 cores | 35-50 |
NSY-153 | 5 cores | JSY-153 | 5 cores | 70-150 |
NSY-154 | 5 cores | JSY-154 | 5 cores | 185-300 |
Typical application
C8.7/15 Heat Shrinkable Cable Accessories
Features:
Dimensions | ||||||
Reference | Reference | Reference | size for conductor | |||
UPM C8.7/15 | UPM C8.7/15 | UPM C8.7/15 | mm2 | |||
NSY-1031 | 3 cores Indoor XLPE Termination | WSY-1031 | 3 cores Outdoor XLPE Termination | JSY-1031 | 3 coresXLPE Cable Joints | 4-35 |
NSY-1032 | WSY-1032 | JSY-1032 | 35-50 | |||
NSY-1033 | WSY-1033 | JSY-1033 | 50-150 | |||
NSY-1034 | WSY-1034 | JSY-1034 | 185-300 |
Technical Data |
Property | Test method | Values | |
Work frequency dry voltage withstand | 45kV/1min | No breakdown and no flashover | |
Work frequency wet voltage withstand | 45kV/1min | No breakdown and no flashover | |
Work frequency long term voltage withstand | 35KV/4hrs | No breakdown and no flashover | |
Impact voltage withstand | 105 kv/±10times | No breakdown | |
D.C.voltage withstand | 52 kV/15min | No breakdown and no flashover | |
Partial discharge(kV, pc) | 13, ≤20 | 13, 10 |