1.General
HVD1-12(VS1-12) type indoor AC HV vacuum circuit breaker (hereinafter referred to as circuit breaker) are suitable for 12kV air-insulated indoor switchgears, used as protection and control unit of power equipment of industrial& mining enterprise. Due to the super excellence, it is especially suitable for location where requires the frequent operation of rated working current or multi breaking short circuit current.
The circuit breaker adopts the integrated design of operating mechanism and circuit breaker body, servers as not only fixed installation, but also the handcart unit through equipping with a special propelling mechanism.
2. Model description
3.Service conditions
3.1 Environment temperature:-15℃~+40℃;
3.2 Environment humidity: Daily average relative humidity:≤95%, monthly average relative humidity:≤90%; Daily average saturated vapor pressure:≤2.2×10-3Mpa,monthly average saturated vapor pressure:≤1.8×10-3Mpa;
3.3 Altitude: Not exceed 1000m;
3.4 Earthquake intensity: Not exceed°ree;
3.5 Service location: No water, flammable or explosive matter, chemical corrosive gas or drastic vibration.
1. Main specifications and technical parameters
NO. |
Item |
Unit |
Parameter |
|||
1 |
Rated voltage |
KV |
12 |
|||
2 |
Rate frequency |
Hz |
50 |
|||
3 |
Rated lightning impulse withstand voltage(1min) |
KV |
75 |
|||
4 |
Rated short-time power frequency withstand voltage (1min) |
KV |
42 |
|||
5 |
Rated short-circuit breaking current |
KA |
20 |
25 |
31.5 |
40 |
6 |
Rated current |
A |
630 1000
|
630 1000
|
1250 1600
|
1600 2000
|
7 |
Rated peak withstand current |
KA |
50 |
63 |
80 |
100 |
8 |
Rated shorted-time withstand current |
KA |
20 |
25 |
31.5 |
40 |
9 |
Rated shorted-time making current(peak) |
KA |
50 |
63 |
80 |
100 |
10 |
Power frequency withstand voltage of secondary circuit(1min) |
V |
2000 |
|||
11 |
Rated operation sequence |
|
Off-0.3s-On&Off-180s- On& Off
|
|||
12 |
Rated breaking current of capacitor bank |
A |
630/400(40kA 800/400) |
|||
13 |
Opening time(rated voltage) |
ms |
20~50 |
|||
14 |
Closing time(rated voltage) |
ms |
30~70 |
|||
15 |
Rated short-circuit current breaking times |
times |
50(40kA 30) |
|||
16 |
Mechanical life |
times |
20000 |
|||
17 |
Rated opening/closing voltage |
V |
AC110, 220; DC110, 220 |
|||
18 |
Rated voltage of energy-storage motor |
V |
AC110, 220; DC100, 220 |
2.Dimensions
3.Outline size
Parameters |
P |
A |
B |
C |
D |
E |
F |
G |
H |
I |
J |
K |
L |
M |
Q |
R |
S |
T |
630A
|
150 |
535 |
502 |
433 |
637 |
76 |
78 |
368 |
275 |
580 |
445 |
280 |
598 |
440 |
275 |
275 |
237 |
430 |
210 |
681 |
652 |
433 |
637 |
76 |
78 |
520 |
275 |
580 |
445 |
280 |
598 |
590 |
275 |
275 |
237 |
430 |
|
1250A
|
150 |
535 |
502 |
433 |
637 |
76 |
78 |
368 |
275 |
580 |
445 |
280 |
598 |
440 |
275 |
275 |
237 |
430 |
210 |
681 |
652 |
433 |
637 |
76 |
78 |
520 |
275 |
580 |
445 |
280 |
598 |
590 |
275 |
275 |
237 |
430 |
|
1250A
|
210 |
681 |
652 |
433 |
637 |
76 |
78 |
520 |
275 |
580 |
445 |
280 |
598 |
590 |
275 |
275 |
237 |
430 |
1600A
|
210 |
681 |
652 |
433 |
637 |
76 |
78 |
520 |
275 |
580 |
445 |
280 |
598 |
590 |
275 |
275 |
237 |
430 |
275 |
881 |
852 |
361 |
698 |
77 |
88 |
720(650) |
310 |
632 |
445 |
295 |
586 |
790 |
310 |
275 |
252 |
462 |
|
2000A
|
275 |
881 |
852 |
361 |
698 |
77 |
88 |
720(650) |
310 |
632 |
445 |
295 |
586 |
790 |
310 |
275 |
252 |
462 |
2500A-3150A
|
275 |
881 |
852 |
361 |
698 |
77 |
88 |
720(650) |
310 |
632 |
445 |
295 |
586 |
790 |
310 |
275 |
252 |
462 |