Model: | - |
---|---|
Brand: | - |
Origin: | - |
Category: | Electronics & Electricity / Other Electrical & Electronic |
Label: | vacuum circuit break , circuit breaker , HVD11-1.14/630 |
Price: |
US $568.7
/ pc
|
Min. Order: | 10 pc |
Last Online:30 Dec, 2014 |
1.Product Summary
This product mainly used in 1140v or 660v three phases electrical distribution system. It is used for distribution power, circuit protection and power equipment. It is also popular in railway, mine, electricity and so on. The product structure is vertical design. Vacuum chamber, electromagnet and latched device is up-down structure. Adjustment and maintenance are easy. It has high breaking ability, high reliability and long working life. Its in and out bus bar is at the back of the circuit breaker. And the bus bar is plug-in type, can be installed as explosion-proof feed switch easily. This circuit breaker should be used together with electronic tripper.
2. The normal working condition
a. Ambient temperature |
-5℃- +40℃ |
b. Altitude |
no more than 2000m |
c. Humidity |
Relative humidity no more than 50% (under ambient temperature: 40℃) |
d. Class of pollution |
3 class |
e. Installation type |
Main circuit Ⅲ, Control circuit Ⅱ |
f. Installation condition |
Vertical installation, inclination degree<15° |
g. Auxiliary switch using type |
AC-15, DC-13 |
3. Model No. and meaning
1.Main technical parameters
a. Rated voltage |
1140v AC |
b. Rated current |
630A |
c. Convention thermal current |
630A |
d. Rated short circuit breaking current |
12.5KA(1140V, COSΦ=0.3) |
e. Rated short circuit breaking times |
16times(Closing-Opening 10 times, Opening 6 tiems) |
f. Rated working frequency |
50HZ |
g. Electrical life |
≥3000times AC-2 |
h. Mechanical life |
≥10000times AC-2 |
i. Inherent closing time |
≤100ms |
j. Inherent opening time |
≤30ms |
k. Three phases unsynchronized time |
<1.5ms |
l. Electromagnet power on time |
120~200ms |
m. Resistance of single phase closing circuit |
≤100μm |
n. Opening distance |
3.0~4.0mm |
o. Over travel distance |
1.8~2.2mm |
p. Auxiliary contacts |
3NO+3NC |
(Table 1, Table 2).
Table 1 Coil parameters
|
Rated working voltage |
Rated working current |
Coil resistance |
Closing coil |
220V AC |
7.2A |
15Ω |
Opening coil |
48V DC |
0.8A |
60Ω |
Under voltage coil |
48V DC |
0.1A |
480Ω |
Table 2 Power frequency withstand voltage test
|
Power frequency withstand voltage |
Testing time |
Main circuit fracture |
10kv |
1min |
Phase to Phase |
3500v |
|
Main circuit to body case |
3500v |
|
Main electromagnet coil to body case |
1500v |
|
Under voltage coil, Opening coil to body case |
500v |
2. Outline dimension drawing
1. Vacuum chamber 2. Overtravel spring 3. Rotating arm 4. Screw 5. Manual tripper 6. Under voltage tripper 7. Axis shaft 8. Holding hook 9. Shunt release