RTKR-990 Battery Charger/Discharger Complex
RTKR-990 is a complex unit which provides one-stop-solution for battery string maintenance. With charging and discharging for same battery string, it will greatly simplify your testing for batteries. Extra functions like real time online monitoring and battery activation will enable you to know your batteries comprehensively. What's more, it is simple-to-use, r ed and portable which will be extensively cost effective and time-saving.
Features
l Light weight, most models are portable within 20kg
l Simple designing and user-friendly interface, easy to operate
l Suitable for all standby batteries and power batteries: 1.2V, 2V, 6V and 12V
l Multi-function in one unit: it uses 3-phase charging, constant current discharging, cell test, real-time online monitor and battery activation
l Multi-condition for operation auto-stop: time out, maximum capacity, minimum voltage threshold (for battery or string)
l It adapts PTC ceramic resistor which secures your discharging
l Lag-out batteries could be automatically sorted, and activation function follow-by could be used to enhance their performance
l As load unit, it uses wireless communication to monitor each single battery instead of merely a load bank
l Graphical display, showing test result with curves
l Direct USB drive for convenient data transfer to PC
l Powerful data view software for complex record analyzing and report printing
l Various configuration applicable to different area of industry like telecom and power utility
Technical Parameter
Parameter |
Testing range |
Resolution and accuracy |
Total discharging voltage |
96~270V (Norm: 220V) 48~135V (Norm: 110V) 21~58V (Norm: 48V) |
Resolution: 10mV Accuracy: 0.1V |
Total charging voltage output |
180~286V (Norm: 220V) 88~143V (Norm: 110V) 38~62V (Norm: 48V) |
Resolution:10mV Accuracy:0.1V |
Charge/discharge cell voltage | 0.000V~16.00V |
Resolution: 1mV Accuracy: 10mV |
Operating Time | 0~99h 59m |
Specifications:
1. Mains: 100-240VAC, 50/60Hz or AC 380V, 3 phase 4 wire
2. Temperature: 0℃~40℃ (Operating) -30℃~70℃ (Storage and transportation)
3. Humidity: 5%~90% Relative Humidity
4. Display: 128*64 pixel LCD screen
5. Protection: thermal cut-off, automatic over load and voltage threshold protection