ZY6014J BS 6387 Circuit integrity under fire conditions apparatus
1. Corresponding standard:
1.1 IEC60331-11:1999《Test for electric cables under fire conditions circuit integrity-Part 11 Apparatus-fire alone at a flame temperature of at least 750℃》;
1.2 IEC60331-12:2002《Test for electric cables or optical fibre under fire conditions circuit integrity-Part 12 Apparatus—Fire with shock at least 830℃》;
1.3 IEC60331-25:1999《Test for electric cables under fire conditions circuit integrity-Part 25 Apparatus—procedures and requirements---rated voltage ≦0.6/1.0KV》
1.4 IEC60331-23:1999《Test for electric cables under fire conditions circuit integrity-Part 23 Apparatus—procedures and requirements--- Electric data cables》
1.5 IEC60331-25:1999《Test for electric cables under fire conditions circuit integrity-Part 25 Apparatus—procedures and requirements--- optical
fiber cables》
2. Main parameters:
Main component: Sample supporting system, trolley, control system, combustion chamber
1)Combustion chamber: It’s fixed on the angle iron. Size: 3MX3MX3M
Optional material (Stainless steel or brick wall)
2) Sample supporting system
The cable sample shall be well fixed on 2 or 3 metal ring.
Diameter of metal ring: 150mm
3)Burner:The source of heat shall be a ribbon type propane gas burner with a nominal burner face length of 500 mm 、width 15mm with Venturi mixer. The face of the burner shall have three staggered rows of drilled holes, nominally 1,32 mm in diameter and drilled on 3,2 mm center distance
4)Flex meter: air :80 L/min , propane : 5 L/min.
5)Main components of burner: pressure regulating valve, flame ignitor ignition, flameout, temperature measurement system, air source, regulating valve , ignition device, gas pipe, flow meter, Venturi mixer, burner, ball valve, air valve, compressed air bottle
6) Counter time: 0 to 99.99s/m/h setting arbitrarily
Ignition : automatic ignition
8)Temperature measurement system: 0~1000oC setting arbitrarily.
9) Circuit : 3 sets of 3000 VA transform, voltage : AC1000V.
electricity : 3 A.