GFDD dry transformer cooling fans
Product Description
Mdoel definition
For example:GFDD470-155
Representing single-phase 220V top blowing type cross cooling blower for dry transformer with the total length of blower of 470mm and the diameter of wheel of Φ155mm
Specification
The appearance、installation dimension and wiring diagram for Top blowing type
Application and maintenance
Power should be conformed with the rated parameter of blower Nameplate; overload protection device of motor is equipped by user.
Please test the insulation resistance before application; the value should be over 2MΩ,and it cannot be less than 0.5 MΩ when thermal state or temperature is higher.
Before operating the blower, please check the blower whether the outlook is fine and the connection is reliable or not; wind wheel spinning well without retardance, otherwise, stop operation and exam it immediately.
User had better operates it not less than an hour per week to avoid components damping and grease lubricant freezing, and it can also clean the inner dust. It should be operated several times if working environment temperature is lower or higher.
It can be repaired, exchanged and returned repaired in a year if the product with quality problems.
|
Product Image
Img 1
Img 2
Send Inquiry to this Member
Related Products of this Company
This member assumes full responsibility for the content of this listing. DIYTrade accepts no responsibility whatsoever in respect of such content.
To report fraudulent or illegal content, please
click here.
China Suppliers Quick Searching:
,