transformer loss and capacity tester

transformer loss and capacity tester
Model:HTRS-V
Brand:Huatian
Origin:Made In China
Category:Electronics & Electricity / Electronic Instrument / Electricity Meter & Instrument
Label:capacity tester , loss tester , transformer loss
Price: -
Min. Order:1 pc
Inquire Now

Product Description

Products features

1. Measure the transformer no-load current, no-load loss; short-circuit voltage, short circuit (load) loss, capacity.

2. Test methods: three-table.

3. The device can auto check if the wire was correctly connected, and display the vector diagram of three phase current, voltage when test the three phase transformer.

4. Single machine can make the loading test for substation transformer under 1600KVA; can make the loading test with 1/3 of the rated current for substation transformer under 2500KVA (the device can convert to the loading losses parameters if the rated current under 1/3 of the rated current)

5. All the related test results are automatically corrected. Instrument can automatically such as: the waveform correction, temperature correction, non-rated voltage correction, calibration, and other non-rated current correction, so that more accurate test results.

6. 320x240 LCD, friendly man-machine interface, brilliance control, adapts to all seasons. 

7. With electronic clock, auto record the data, time, it is good for saving and managing the test results.

8. Panel type printer can print the test results on site.

9. Data (specimen setting, test results, measurement time) can be saved on power failure and can be reviewed, it can store 500 groups test results, can connect with computers to transmit data. 

10. Allow external connecting CT and PT to make extension measurement, can test the specimen with any parameters. 

 

Product parameters

  • Service conditions

Temperature:-5°C40°C

Humidity<95%25°C

Altitude<2500m

Outside interference: no exceptionally strong vibration, no extra - strong electromagnetic fields.

Power supply: 220VAC±10%45Hz~55Hz.

  • Main technical parameters

Capacity measuring range: 30kVA ~ 31500kVA

Current measuring range: 0 -100A auto-switch the measurement range

Current measurement accuracy: ± (0.2% + 3digits)

Voltage measurement range: Line Voltage0-750V; phase voltage 0-450V,     auto-switch the measurement range

Voltage measurement accuracy: ± (0.2% + 3digits)

Insulation resistance: > 100MΩ

Leakage current: <3.5mA

Dielectric strength: the power connection on the chassis can withstand: 1500V

External transformer can broaden the scope of measurement instruments

Frequency Range: 40 ~ 65Hz, accuracy class 0.2

Power Input: AC220V ± 10%

  • Insulating strength
  • Insulation resistance Voltage, current input terminal to the cabinet≥100M.
  • Working power input terminal to the shell withstands frequency 2KV (RMS). which lasted one minute experiment.
  • Others 

Dimension: 400x300x220mm

Weight: 12KG (not including wires)

 

transformer loss and capacity tester 1

Member Information

Wuhan Huatian Electric Power Automation CO., LTD.
Country/Region:Hu Bei - China
Business Nature:Manufacturer
Phone:13871549150
Contact:Amy (Sales Manager)