Model: | NCS-PT105 |
---|---|
Brand: | Microcyber |
Origin: | Made In China |
Category: | Electronics & Electricity / Electronic Instrument / Pressure Gauge |
Label: | Pressure transmitter , Differential , HART pressure |
Price: |
US $1
/ pc
|
Min. Order: | 1 pc |
4-20mA Pressure Transmitter (HART Protocol)
As a new generation of smart fieldbus pressure transmitter, NCS-PT105II series pressure transmitter with capacitance sensor is available on FF H1, Profibus PA and HART protocols. The Transmitter has high accuracy, better reliability and intrinsically safety.
Features:
1.Excellent performance:
High accuracy: ±0.075%(20°C, range rate 10:1)
Stability: ±0.1% of maximum range per year
High range rate: 100:1
2.Multi sensor: differential pressure (SD), high static pressure (SH), gauge pressure (SG), absolute pressure (SA), micro differential pressure (SR)
3.Compensation: automatically environmental temperature compensation
Basic Parameter
Measure object |
Liquid, gas, stream |
|
Power |
9~32V DC(FF,PA) 9~32V dc (FF, PA Explosion-proof instrument) 11.9~42 V DC (HART) 11.9~30 V DC (HART Explosion-proof instrument) |
|
Output |
Analog: 2 wire 4~20mA Digital: HART, FF and PA signal |
|
Load resistant |
0~1500ohm (common) 250~550ohm (with HART) |
|
Insulation |
Input and output insulating voltage: 500Vrms (707VDC) |
|
Display |
Optional 6 bits digital number or 5 bits characters LCD display |
|
Temperature scale |
Work temperature: -40 - 85°C (No display) -30 - 70°C (display) -30 - 60°C (Explosion-proof) Store temperature: -40 - 100°C (No display) -40 - 85°C (display) |
|
Allowed media temperature measured |
-40 °C - 110 °C (Type name include ‘IC’) -40 °C - 149 °C (silicone oil) -40 °C - 204 °C (sylthlem800) -18 °C - 204 °C (inert liquid) -40 °C - 104 °C (others) |
|
Humidity scale |
5%-100%RH |
|
Start time |
≤ 5 seconds |
|
Refresh time |
0.2 seconds |
|
Dump adjusting |
Time constant 0-15 seconds |
|
Change of cavity |
< 0.16 cm3 |
|
Static pressure limit |
SR |
Range 2: 1000psi (6.89MPa) |
SD |
Range 3-8: 2000psi (13.8MPa) |
|
SG |
Range 3-8: 2000psi (13.8MPa) Range 9: 4500psi (31.0MPa) Range 0: 7500psi (51.7MPa) |
|
SA |
Range 4: 58psi (400kPa) Range 5: 218psi (1500kPa) Range 6: 435psi (3000kPa) |
|
SH |
Range 4-7: 4500psi (31.0MPa) |
Performance Index
Precision |
For range 2 ±0.1% of Span is for 0.5 URL≤Span ≤ URL; ±[0.05+0.025 ×(URL / Span)]% of Span is for Span<0.5 URL. For other ranges ±0.075% of Span is for 0.1 URL≤Span ≤ URL; ±[0.025+0.005 ×(URL / Span)]% of Span is for Span<0.1 URL |
Temperature effect |
Total effects per 28°C(50°F)change: For range 2 ±[0.05% URL +0.25% Span] For other ranges Span≥0.1 URL: ±[0.019% URL +0.125% Span] Span<0.1 URL: ±[0.025% URL +0.125% Span] |
Long time stability |
In 12 months, ±0.1% of maximum range |
Static pressure effect |
For range 2 ±1% / 13.8MPa For range 3 ±0.5% / 13.8Mpa For other ranges ±0.25%/13.8MPa |
Location installed effect |
The maximum of the zero point movement is 0.24kPa |
Power effect |
< 0.005%/V of range calibrated |
Explosion-proof |
intrinsically safety Ex ia II C T4 |
Explosion-proof level |
IP65 or IP67 |
Vibration effect |
Meet GB/T 2423-1995 |
Electromagnetic compatibility |
Meet GB/T 17626-1998 (IEC 61326-1:1997) |
Microcyber Corporation | |
---|---|
Country/Region: | Liao Ning - China |
Business Nature: | Manufacturer |
Phone: | 13889336426 |
Contact: | Lisa Liu (sales) |
Last Online: | 12 May, 2016 |