MAIN SPECIFICATIONS OF GENERATOR SETS |
GENSET MODEL |
P68 |
P72 |
P80 |
P91 |
P108 |
Continuous output (KW/KVA) |
68 / 85 |
72 / 90 |
80 / 100 |
91 / 114 |
108 / 135 |
Standby output (KW/KVA) |
75 / 94 |
80 / 100 |
88 / 110 |
100 / 125 |
120 / 150 |
TECHNICAL DATA |
DIESEL ENGINE MODEL |
1006TG1A |
1006TG1A |
1006TG2A |
1006TAG |
1006TAG |
Engine Characters |
Water-cooled,in line,6-cylinders,4-stroke,direct injection,dry cylinder liner,1500rpm (50Hz)/1800 rpm(60Hz) |
Constant output (KW) |
84.3 |
84.3 |
92.3 |
121 |
121 |
Standby output (KW) |
92.7 |
92.7 |
102 |
134 |
134 |
Aspiration |
Turbocharged |
Turbocharged |
Turbocharged |
Turbocharged |
Turbocharged and aftercooled |
Bore(mm)×Stroke(mm) |
100×127 |
100×127 |
100×127 |
100×127 |
100×127 |
Cubic Capacity(Liters) |
5.99 |
5.99 |
5.99 |
5.99 |
5.99 |
Piston Speed(m/s) |
6.35 |
6.35 |
6.35 |
6.35 |
6.35 |
Compression Ratio |
16:1 |
16:1 |
16:1 |
17:1 |
17:1 |
Stability bandwidth |
≤±0.8% |
≤±0.8% |
≤±0.8% |
≤±0.25% |
≤±0.25% |
Steady governing rate |
≤5% |
≤5% |
≤5% |
≤1% |
≤1% |
Acoustic Pressure |
≤92.1dBA(At full load, 1m distance) |
≤94.3dBA |
≤94.9dBA(At full load, 1m distance) |
Exhaust Temperature:℃ |
545 |
545 |
550 |
571 |
571 |
Exhaust Back PRESSURE |
6KPa |
6KPa |
6KPa |
6KPa |
6KPa |
Air Induction System |
Dry element type with back pressure warning indication |
Lube Temperature / Capacity |
125℃ / 16.1L(Max.) |
125℃ / 16.1L(Max.) |
125℃ / 16.1L(Max.) |
125℃ / 19L(Max.) |
125℃ / 19L(Max.) |
BMEP:kPA (Prime power) |
1283 |
1283 |
1404 |
1964 |
1964 |
Heat Rejection to Exhaust |
59.1 kW/min |
59.1 kW/min |
66.5 kW/min |
115 kW/min |
115 kW/min |
Heat Rejection to Cooling |
56 kW/min |
56 kW/min |
63 kW/min |
65.5 kW/min |
65.5 kW/min |
Cooling System Volume |
27.7L |
27.7L |
27.7L |
37.2L |
37.2L |
Cooling Air Flow |
135 m ³/min |
135 m ³/min |
135 m ³/min |
154 m ³/min |
154 m ³/min |
Combustion Air Fiow |
5.74 m ³/min |
5.74 m ³/min |
5.74 m ³/min |
8.38 m ³/min |
8.38 m ³/min |
Exhaust Gas Flow |
15.56 m ³/min |
15.56 m ³/min |
16.24 m ³/min |
24.14 m ³/min |
24.14 m ³/min |
Min. Fuel Consumption |
≤205 g/kW.h |
≤205 g/kW.h |
≤205 g/kW.h |
≤205 g/kW.h |
≤205 g/kW.h |
Lube Consumption |
≤1.36g/kW.h |
≤1.36g/kW.h |
≤1.36g/kW.h |
≤1.36g/kW.h |
≤1.36g/kW.h |
ALTERNATOR MODEL |
With Stamford, Leroy Somer, Marathon or other branded alternators etc. |
Continuous output (KW/KVA) |
68 / 85 |
80 / 100 |
80 / 100 |
91 / 114 |
112 / 140 |
Power Efficiency |
90.2% |
90.4% |
90.4% |
90.8% |
91.7% |
Voltage Regulation |
±1.0% with 4% engine governing |
Waveform Distortion |
No lode <1.5% and non-disttorting balanced linear load <5% |
THF / TIF |
<2% / <50 |
<2% / <50 |
<2% / <50 |
<2% / <50 |
<2% / <50 |
Dimensions (L×W×H) (mm) |
2480×710×1480 |
2480×710×1480 |
2480×710×1480 |
2580×800×1480 |
2580×800×1480 |
Net Weight (kg) |
1440 |
1490 |
1500 |
1520 |
1600 |