K-13 isolation transformer

K-13 isolation transformer
Model:-
Brand:Wapower
Origin:Made In China
Category:Electronics & Electricity / Power Transmission Equipment & Transformer
Label:K-factor , isolation transforme , K rated
Price: ¥600 / pc
Min. Order:1 pc

Product Description

Product introduction
There are triple harmonic and other odd times harmonic in the power network and the user load. The zero-sequence third harmonic can cause increased neutral line current and other odd times harmonic additional heating in the winding. K-factor transformer is specially designed to withstand harmonic. According to the specifications of 
ANSI/IEEE C57.110-1986K= ∑ LH (PU) h. K-factor ranges from 1 to 50. 1 indicates a linear load(no harmonic) and 50 terribly harmonic environment. The larger the K-factor, the stronger the capacity of eliminating harmonic interference of the transformer.



According to ANSI/IEEE C57.110, the harmonic content processed by K-13 transformer are as following: 

Harmonic(h) Curent(lh) Ih(pu) lh(pu)2h2
1 100.000% 1.000 1.000
3 33.333% 0.333 1.000
5 20.000% 0.200 1.000
7 14.286% 0.143 1.000
9 11.111% 0.111 1.000
11 9.091% 0.091 1.000
13 7.692% 0.077 1.000
15 6.667% 0.067 1.000
17 5.882% 0.059 1.000
19 5.263% 0.053 1.000
21 4.762% 0.048 1.000
23 4.348% 0.043 1.000
25 4.000% 0.040 1.000

 

Technical parameter:
1, Power range ≤1000KVA 
2. Switching current  4Ie

3. Common-mode attenuation ≥120db 

4. Dielectric strength: core-winding, winding-shielding, winding-earth 3000 VAC / 50Hz / 60s no arcing or breakdown

5. Insulation resistance: 500VDC, Insulation resistance value  100M

6. Noise level < 65db (The testing point's horizontal distance from transformer shall be 1 metre.)

7. Protection grade: IP00

8. Insulation class: H

9. Product standardsUL15612000 Dry-type general power transformer
 

Application environment and conditions:
1, The altitude is not more than 1000 meters and if more than 1000 meters, derating is required.
2, Running temperature: -5 ℃-40 ℃, relative humidity is less than 90%. 
3, Without harmful gas, inflammable, explosive and conductive dust around.

Payment Terms:T/T
K-13 isolation transformer 1

Member Information

Shenzhen Wapower Electrical Technology Co., Ltd.
Country/Region:Guang Dong - China
Business Nature:Manufacturer
Phone:17180597652
Contact:Becky Huang (Foreign Trade Sales)
Last Online:21 Oct, 2016