Home > Products > Electronics & Electricity > Other Electrical & Electronic

MART6-C3-60-250 1
  • MART6-C3-60-250 1

MART6-C3-60-250

Model:MART6-C3-60-250
Brand:-
Origin:Made In Taiwan, China
Category:Electronics & Electricity / Other Electrical & Electronic
Label:SPD , Surges , SEAT
Price: -
Min. Order:-
Inquire Now

Member Information

Detail

Hichance Technology

Free MemberTaiwan, China
Last Online:18 Jan, 2019

Product Description

♦  Types of surge suppressed:
    Lightning Flash Surges, Power switching surges , Switching Inrush Current , and Electric Magnetic Pulse.

♦  Method of handling surge energy:
    Series mode surge energy absorbed and transferred to voltage.

♦  Installation:
    Setup on wall, on table, in cabinet of electronic instruments.

♦  Indicates function:
    Records the number of times of invading interference sources digitally, and indicates the status of module activities and the status of the SET devices functionality.

 Case of Devices:
    Metal structure case with anode treatment and sand blasting to prevent EMI interference of itself

♦  Suitable AC voltage:
    AC 100V-250V 50/60Hz ±10%.

♦  Max. load current allowed:
    1ψ3W 60A.(Use 14mm2 hypalon wire connect to loads)

 Max. power capacity:
    15kW.

♦  Input Impedance (R) without loads:
    >10MΩ.

♦  Core module temperature of 60A load:
    Less than 65 oC.

♦  Surge immunity:
    1.2x50μs,10kV; 8x20μs,5kA combination wave, 20 sec interval, at least 3 times.

 Surge energy absorbing rate:
    1.2x50μs,10kV; 8x20μs,5kA combination wave, 99%±1% (ungrounding condition).

♦  After surge invasion, AC waveform recovering time:
    Less than10mS.

♦  After surge invasion, AC waveform correction ability:
    1-3A load condition, more than 3 cycles.

♦  EMP(fast transient/bust) immunity:
    4.5kV, 5x50ns EFT waveform, 95%±2% (ungrounding
 condition).

 Loads remnant voltage:
    650V±20% under combination wave tested.

♦  Load protection mode:
    L-N, L-G, and N-G.

♦  System ground resistance demand:
    None.

♦  Operation temperature range and humidity range:
    -40 to +85oC, 35 to 95% relative humidity (no dew).

♦  Dimension:
    Base 167mm (L)/127mm(W)/ Cover 167mm (L)/127mm(W)/62mm(H) ±1%.

 Weight:
    1,400g ±5%.

♦  Confirm standards:
    ANSI C62.41、IEC 61000-4-5、IEC 61000-4-4、IEC 61643-1、ANSI C37.90.1etc.

♦  Surge-testing:
    On-line condition, tested by10kV/5kA combination wave, 4.5kV, 5x50ns EFT wave.


Product Image

MART6-C3-60-250 1
Img 1

Send Inquiry to this Member

Hichance Technology

2F.,No.16,Ln.1,Fushan Rd., Wenshan Dist,Taipei City,116,Taiwan

Phone:
886-2-29366358
Fax:
886-2-269366352
Contact:
Paul Hsu (GM)
Mobile:
932152734

Related Products of this Company

This member assumes full responsibility for the content of this listing. DIYTrade accepts no responsibility whatsoever in respect of such content.
To report fraudulent or illegal content, please click here.

China Suppliers Quick Searching:

Other Electrical & Electronic Made In China Products

,  

Other Electrical & Electronic China Suppliers and China Manufacturers